Trip Table
66551111
K
Keeyyppaadd
D
Diissppllaayy
66990011
K
Keeyyppaadd
D
Diissppllaayy
D
Deessccrriippttiioonn
P
Poossssiibbllee R
Reeaassoonn ffoorr TTrriipp
ATN8
MAX RPM DATA
ERR
♦
This error is reported when the MAX SPEED RPM is
set to a value outside the range for which Autotune has
gathered data. Autotune gathers data on the motor
characteristics up to 30% beyond “max speed rpm”. If
MAX SPEED RPM is later increased beyond this range,
the drive had no data for this new operating area, and
so will report an error. To run the motor beyond this
point it is necessary to re-autotune with MAX SPEED
RPM set to a higher value.
STAC
STACK TRIP
♦
The drive was unable to distinguish between an
overcurrent/desat or overvoltage trip
ATNA
LEAKGE L
TIMEOUT
♦
The leakage inductance measurement requires a test
current to be inserted into the motor. It has not been
possible to achieve the required level of current.
Check that the motor is wired correctly.
PLOS POWER LOSS STOP
♦
Power Loss Stop sequence has ramped Speed
Setpoint to zero or timed out
ATNC
MOTR TURNING
ERR
♦
The motor must be stationary when starting the
Autotune