[PROFIBUS – operation mode]
Positioning
[PLC -> Compax3]
CW 1
Commanded positioning value (XCOMMANDED_A)
Commanded motion speed D (32 Bit)
Commanded acceleration B (32 Bit)
[Compax3 -> PLC]
SW 1
Actual position value XACTUAL_A
Actual speed value NACTUAL_B (32 Bit)
[Operation Mode Settings]
Acyclic process data channel / Parameter channel
Select with "PKW"
Error response on fieldbus failure is up to user.
\\ I20T11 drive configuration \ I/O - assignment
Selection:
-
free
-
Fixed assignment
It is recommend to select „free“. With „Fixed assignment“ are used some Binary
connections between control word and digital inputs (E0 ... E3), that cases if there is no
plug at X12 the C3 is not possible to be controlled.
3.2 Compax3 Hardware
DIP Switch: Bus address
Bus plug: ``ON / OFF`` Bus termination resistance
3.3 3.3 SIMATIC - HW Config
Correlated to PPO-Type which is shown in the C3 configuration it is needed to select at
SIMATIC - HW Config this type: