background image

Bulletin TI-FID1000C 

FID 1000 and 2500 Gas Stations

Parker Hannifin Corporation

Filtration and Separation Division

Haverhill, MA • 1-800-343-4048 

www.parker.com/ags

4

Note: All  installation, operation and maintenance activities for the FID Gas Stations should 
be performed by suitable personnel using reasonable care.

The FID 1000 and FID 2500 generators are a free-standing bench-top unit.

  Do not suspend the 

generator from the wall or ceiling.

  The weight and size could pose a falling hazard.  The gen-

erator should be located indoors, protected from severe weather conditions and free from exces-
sive ambient, dust or dirt.

  Do not install the generator outdoors.

The ambient temperature of the air surrounding the generator must be between 60°F-100°F (16°C-
40°C ).

  Do not place the generator where there is a chance of freezing.  

Place the generator 

in an upright position, on a level surface, in close proximity to the electrical power supply and the 
equipment requiring both hydrogen and hydrocarbon-free air.

The Zero Air Generator compressed air inlet port is brass 1/4" female NPT.  The inlet port is lo-
cated at the top center of the generator.  The Zero Air outlet port is brass 1/8" compression union, 
located below the Inlet port.  Male 1/4" NPT compressed air inlet pipe fittings

 

rated for 125 psig  

(8.5 Barg) line pressure should be used to connect to the generator.  

The Hydrogen vent is also 

a brass 1/4" female NPT, located at the right hand side of the generator and the Hydrogen 
outlet is a SS  1/ 8" Compression Union, located directly below the hydrogen vent.

A shut-off valve and a pressure regulator should be installed directly upstream from the Parker 
Balston Zero Air generator.  The shut-off valve isolates the unit from the air line for maintenance 
and troubleshooting tasks.  The pressure regulator controls the inlet air pressure and should be set 
to maintain a constant pressure between 40 psig and 125 psig (2.7 barg and 8.5 barg ).  Maintain-
ing a constant inlet air pressure will minimize system pressure fluctuations which may affect the 
purity of the zero grade air.  Parker offers a pressure regulator, complete with a pressure gauge, as 
an accessory (P/N 72-130-V883).

The FID 1000 and FID 2500 Gas Stations should be located in close proximity to the electrical 
power supply, and the downstream equipment to which it supplies both Hydrogen and Zero grade 
air.  There is no limit to the distance between the generator and the point of use as long as tubing 
size, cleanliness, and pressure drop are taken into consideration.  The generator should be located 
indoors, protected from severe weather conditions.  The installation location should be free from 
excessive ambient dust or dirt. 

 Do not install the generator outdoors.

  The ambient temperature 

of the air surrounding the generator must be between 60°F-100°F (16°C-40°C) to ensure optimal 
operation of the unit.

 

See page 18 for a list of the symbols displayed on the generator and referred to in this Manual.

The FID 1000 and FID 2500 generator weigh 53 lbs (24 kg).  Use proper equipment and lifting 
techniques for transporting this equipment to its installation location.  The FID/Hydrogen is intended 
to remain stationary when filled with water.  If necessary, the generator may be transported over 
short distances when filled.

  Do not grasp the front panel Bezel when moving the generator; 

lift only from the bottom.  Keep the generator in an upright position.

Remove all red tape from the top cover, the back panel, and any other surfaces. Open the top 
cover of the FID Gas Station. Unscrew the dessicant cartridge cap (see Figure 6) and remove the 
red tape covering the outlet port located on the inside of the dessicant cartridge housing. Remove 
the red caps/tape sealing the back panel outlet fittings.

Dessicant -

 Wipe any drops of moisture with a lint free cloth or paper towel from  the dessicant 

cap and housing. Remove the dessicant cartridge from the sealed bag. Use a drop of deionized 
water to wet the o-rings.  Insert the cartridge into the housing, nipple end first (see Figures 7,8, and 
9).

 

 Firmly push down on the cartridge to create a hydrogen-tight seal at the bottom of the housing, 

making sure the cartridge is seated.

Before replacing the dessicant cartridge cap, make sure the large Viton o-ring is centered inside 
the cap (see Figure 9).  Screw the cap on and tighten securely by hand.  Make sure that the o-ring 
is centered and that the o-ring has created a dark ringed seal.

Note:   

Most leaks occur due to improper sealing of the cap to the housing on the dessicant car-

tridge.

Preparation

Installation and Operation

Installation and Operation

General

Location

Symbols

Transporting

Содержание Balston FID 1000

Страница 1: ...source of hydrocarbon free air This will purify on site compressed air to a total hydrocarbon concentration of less than 0 1 ppm measured as methane The ZAG may be used to generate fuel for Flame Ioni...

Страница 2: ...and particulate contamination from the incoming compressed air supply The pre lter assembly is equipped with an solenoid autodrain to eliminate any liquids which have accumulated within the lter hous...

Страница 3: ...urs inside the electrochemical cell assembly Figure 3 Positively charged hydrogen ions are transported across the solid polymer electrolyte along with excess water molecules The hydrogen ions then rec...

Страница 4: ...ould be located in close proximity to the electrical power supply and the downstream equipment to which it supplies both Hydrogen and Zero grade air There is no limit to the distance between the gener...

Страница 5: ...cal power supply voltage Note NA versions of the generator are designed for 120 VAC operation only Deionized Water The FID 1000 and FID 2500 hydrogen must be supplied with deionized water with a resis...

Страница 6: ...d is located at the top center of the rear panel Inlet tubing and ttings should be clean and rated for 125 psig 8 5 Barg minimally The tubing and ttings used downstream from the FID 1000 and FID 2500...

Страница 7: ...iltration and Separation Division Haverhill MA 1 800 343 4048 www parker com ags 7 Figure 6 Unscrew desiccant cap Figure 7 Insert new desiccant cartridge Figure 8 Press down rmly on desiccant to seat...

Страница 8: ...ly The FID Gas Station H2 must be supplied with deionized water with a resistivity of at least 5 Meg Ohm cm or greater Both a Gravity Feed and a Pressure Feed Tubing assembly can be located in the Acc...

Страница 9: ...he device until the desired water level is visible through the Front Panel Display Replace the cap and close the side cover lid It will take approximately 2 liters of deionized water to ll the generat...

Страница 10: ...er in the reservoir above the REFILL line at all times or ensure that the FID Auto ll is directly connected to a DIO water source 2 Minimize the dead volume in the piping between the generator and the...

Страница 11: ...carbons HYDROGEN Over ow in Use 0 0 0 psi ZERO AIR At temperature HYDROGEN in Use 79 66 5 psi ZERO AIR At temperature HYDROGEN add water in Use 79 66 5 psi ZERO AIR At temperature PARKER HANNIFIN ZERO...

Страница 12: ...ipment 3 Fill the DIO Reservoir at least half full with deionized water Make sure that the cell has at least 2 5cm of water showing in the cell assembly tube This can be viewed through the vents in th...

Страница 13: ...external system piping for leaks Shutdown then restart generator Check internal system piping for leaks Shutdown then restart generator No Hydrogen Delivered Check power connections see above Check w...

Страница 14: ...lletin TI FID1000C FID 1000 and 2500 Gas Stations Parker Hanni n Corporation Filtration and Separation Division Haverhill MA 1 800 343 4048 www parker com ags 14 Figure 12 FID Gas Station Exploded Vie...

Страница 15: ...rade BXE pre lter will be accessible from the side of the generator after the generator cover is removed The lter cartridge inside the housing should be changed on an annual basis to maintain ef cient...

Страница 16: ...astic parts in the genera tor These uids may cause cracking and crazing which leads to part failure Use a solution of 4 5 ml of liquid dish soap in one liter of water Re ll the water in the generator...

Страница 17: ...ration Filtration and Separation Division Haverhill MA 1 800 343 4048 www parker com ags 17 Figure 14 View Toward Rear of Unit Model FID 2500 Figure 15 Thermocouple wire Figure 16 Rear View FID 2500 s...

Страница 18: ...one hour to remove any residual oxygen and moisture from the instrument and piping downstream When the desiccant becomes saturated with moisture the blue indicating color will turn beige or gray or t...

Страница 19: ...he fuses in the FID gas station may burn out The fuses are located in the power receptacle on the back side of the generator Before servicing the fuse turn the unit off and disconnect the power cord f...

Страница 20: ...e 40 125 psig 2 7 barg 8 5 barg 40 125 psig 2 7 barg 8 5 barg Altitude 2000 M 2000 M Electrical Requirements 100 120 200 240 VAC 47 63Hz 100 120 200 240 VAC 47 63Hz Power Consumption 480 Watts 110 vac...

Страница 21: ...ay be hot and could cause burns to the skin found on inside of some units Under certain conditions metal cabinet will be warm to touch 70 C 3 Explanation of Warning Symbols Parker Hanni n UK Ltd Filte...

Отзывы: