6. PREVENTATIVE MAINTENANCE
The recommended service procedures identified below, along with all other repair and calibration work,
should be undertaken by a Parker Hannifin-approved technician.
Figure 15 details the service intervals for the ALIGN Multi-Gas Generator. Failure to follow these intervals
may void the warranty.
DO NOT perform service or cleaning on the generator while it is plugged in.
6.1. Cleaning
Inspect the inlet air duct underneath the rear of the generator daily to ensure it is unobstructed and clear of
dust and debris.
If required, clean the outside of the generator with a damp cloth. Avoid excessive moisture around any electri
-
cal sockets and labels. A mild detergent may be used, however, do not use abrasives or solvents.
6.2. Service Kits
12 month Service Kit
Required Every 8000Hrs or 12 Months (Whichever Comes First).
Part Number: MKALIGN-MG-1
V-Belt
Carbon Tower
BX-Filter Element
DX-FIlter Element
Water Separator
Intake Filter
Tip Seals
Pipe Sleeve
Drain Silencer
Particulate Filter
Eco Drain Assy
Kit Part Number
12 Months / 8,000
Hours
24 Months / 16,000
Hours
36 Months / 24,000
Hours
48 Months / 32,000
Hours
MKALIGN-MG-1
X
X
X
MKALIGN-MG-2
X
Figure 15
Grease Gun Kit
IOM_PKR_Align Multi-Gas Generator_022021.indd 17