9-6
Setup Wizard
AC30V series Variable Speed Drive
These parameters are shown when the Profibus DPV1 option is fitted.
PNO
Parameter
Comment
0044
Comms Required
PROFIBUS DPV1
Refer to Profibus DP-V1 Technical Manual HA501837U001
0238
Profibus Node Address
●
0048
Comms Trip Enable
●
These parameters are shown when the Profinet IO option is fitted.
PNO
Parameter
Comment
0044
Comms Required
PROFINET IO
Refer to Profinet IO Technical Manual HA501838U001
0199
Address Assignment
●
0200
Fixed IP Address
●
0201
Fixed Subnet Mask
●
0202
Fixed Gateway Address
●
0203
Option Web Enable
●
0048
Comms Trip Enable
●
On-board Ethernet
Configuration of the on board Ethernet option.
PNO
Parameter
Comment
Setup Base Ethernet
Select TRUE to configure the on board Ethernet port. Select FALSE to skip this section
0929
DHCP
0930
Auto IP
0933
User IP Address
Only visible if DHCP and Auto IP are both FALSE.
0934
User Subnet Mask
Only visible if DHCP and Auto IP are both FALSE.
0935
User Gateway Address
Only visible if DHCP and Auto IP are both FALSE.
Setup Base Modbus
Select TRUE to configure the on board Ethernet port to also act as a Modbus IP client. Select FALSE to skip the
following parameters
0939
Maximum Connections
Sets the maximum number of Modbus clients allowed. If set to zero, then no connections will be allowed.
0942
Modbus Trip Enable
Set TRUE to enable the Modbus Trip. The parameter
Modbus Timeout
must be set to a value other than zero
0940
High Word First
If set to TRUE, the most significant word of a 32-bit parameter will be mapped to the first register, and the least
significant word to the next register.
0941
Modbus Timeout
Sets the process active timeout
Autotune Parameters
Autotune enable and autotune mode. To run the autotune process, complete the wizard then run the drive.
PNO
Parameter
Comment
0255
Autotune Enable
Select TRUE to enable a motor autotune next time the motor is started. (Only visible for induction motor
sensorless vector control mode).
Finalising Setup
Once the Setup Wizard has been run to completion the feature is automatically disabled. Re-starting the drive will not cause the Setup Wizard to
be run again. (If it is desired to re-run the Setup Wizard, this can be achieved as detailed above in “Starting the Setup Wizard”).
Содержание AC30V Series
Страница 33: ...4 15 Installation AC30V series Variable Speed Drive Wiring Diagrams APPLICATION 0 BASIC SPEED CONTROL...
Страница 34: ...Installation 4 16 AC30V series Variable Speed Drive Basic Speed Control Wiring...
Страница 35: ...4 17 Installation AC30V series Variable Speed Drive APPLICATION 1 AUTO MANUAL CONTROL...
Страница 36: ...Installation 4 18 AC30V series Variable Speed Drive Auto Manual Control Wiring...
Страница 37: ...4 19 Installation AC30V series Variable Speed Drive APPLICATION 2 RAISE LOWER TRIM...
Страница 38: ...Installation 4 20 AC30V series Variable Speed Drive Raise Lower Trim Wiring...
Страница 39: ...4 21 Installation AC30V series Variable Speed Drive APPLICATION 3 PRESETS SPEEDS...
Страница 40: ...Installation 4 22 AC30V series Variable Speed Drive Presets Speeds Wiring...
Страница 41: ...4 23 Installation AC30V series Variable Speed Drive APPLICATION 4 PID CONTROL...
Страница 42: ...Installation 4 24 AC30V series Variable Speed Drive PID Control Wiring...
Страница 162: ...Sequencing Logic B 2 AC30V series Variable Speed Drive SEQUENCING DIAGRAM...
Страница 174: ...Compliance C 8 AC30V series Variable Speed Drive Conducted Emissions Profile Unfiltered Product Frame D Frame E Frame F...
Страница 277: ...D 80 Parameter Reference AC30V series Variable Speed Drive Setpoint Drive Frequency Frequency 1 Frequency 2...
Страница 325: ...E 2 E Plan Library AC30V series Variable Speed Drive Which then brings up the E Plan page...