Parameter Reference
D-111
AC30V series Variable Speed Drive
PNO
Name
Path(s)
Type
Default
Range
Units
WQ
View
Notes MBus
0485
Ramp Type
Parameters::Motor Control::Ramp
USINT
(enum)
0
0:LINEAR
1:S RAMP
ALWAYS
TECHNICIAN
01497
0486
Acceleration Time
Same as PNO 484
TIME
10.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01499
0487
Deceleration Time
Same as PNO 484
TIME
10.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01501
0488
Symmetric Mode
Parameters::Motor Control::Ramp
BOOL
FALSE
ALWAYS
TECHNICIAN
01503
0489
Symmetric Time
Parameters::Motor Control::Ramp
TIME
10.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01505
0490
Sramp Continuous
Parameters::Motor Control::Ramp
BOOL
FALSE
ALWAYS
TECHNICIAN
01507
0491
Sramp Acceleration
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s²
ALWAYS
OPERATOR
01509
0492
Sramp Deceleration
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s²
ALWAYS
TECHNICIAN
01511
0493
Sramp Jerk 1
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³
ALWAYS
TECHNICIAN
01513
0494
Sramp Jerk 2
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³
ALWAYS
TECHNICIAN
01515
0495
Sramp Jerk 3
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³
ALWAYS
TECHNICIAN
01517
0496
Sramp Jerk 4
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³
ALWAYS
TECHNICIAN
01519
0497
Ramp Hold
Parameters::Motor Control::Ramp
BOOL
FALSE
ALWAYS
TECHNICIAN
01521
0498
Ramping Active
Parameters::Motor Control::Ramp
BOOL
NEVER
TECHNICIAN
01523
0499
Ramp Spd Setpoint Input
Parameters::Motor Control::Ramp
REAL
x.x
-200.0 to 200.0
%
NEVER
TECHNICIAN
01525
0500
Ramp Speed Output
Parameters::Motor Control::Ramp
REAL
x.x
-200.0 to 200.0
%
NEVER
TECHNICIAN
01527
0501
Jog Setpoint
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%
ALWAYS
TECHNICIAN
01529
0502
Jog Acceleration Time
Parameters::Motor Control::Ramp
TIME
1.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01531
0503
Jog Deceleration Time
Parameters::Motor Control::Ramp
TIME
1.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01533
0504
Stop Ramp Time
Same as PNO 484
TIME
10.000
0.000 to 600.000
s
ALWAYS
TECHNICIAN
01535
0505
Zero Speed Threshold
Parameters::Motor Control::Ramp
REAL
0.1
0.0 to 100.0
%
ALWAYS
TECHNICIAN
01537
0506
Zero Speed Stop Delay
Parameters::Motor Control::Ramp
TIME
0.500
0.000 to 30.000
s
ALWAYS
TECHNICIAN
01539
0507
Quickstop Time Limit
Parameters::Motor Control::Ramp
TIME
30.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01541
0508
Quickstop Ramp Time
Parameters::Motor Control::Ramp
TIME
0.100
0.000 to 600.000
s
ALWAYS
TECHNICIAN
01543
0509
Final Stop Rate
Parameters::Motor Control::Ramp
REAL
1200
1 to 4800
Hz/s
ALWAYS
TECHNICIAN
01545
0511
Motor Type
Advanced Setup::Motor Control::Control and Type
Parameters::Motor Control::Control Mode
USINT
(enum)
0
0:INDUCTION MOTOR
1:PMAC MOTOR
STOPPED TECHNICIAN
01549
0512
Control Strategy
Same as PNO 511
USINT
(enum)
0
0:VOLTS - HERTZ CONTROL
1:VECTOR CONTROL
STOPPED TECHNICIAN 4
01551
0515
Speed Loop Pgain
Parameters::Motor Control::Spd Loop Settings
REAL
20.00
0.00 to 3000.00
ALWAYS
TECHNICIAN 4
01557
0516
Speed Loop I Time
Parameters::Motor Control::Spd Loop Settings
TIME
0.100
0.001 to 1.500
s
ALWAYS
TECHNICIAN 4
01559
0517
Speed Loop Int Defeat
Parameters::Motor Control::Spd Loop Settings
BOOL
FALSE
ALWAYS
TECHNICIAN 4
01561
0518
Speed Loop Int Preset
Parameters::Motor Control::Spd Loop Settings
REAL
0
-500 to 500
ALWAYS
TECHNICIAN 4
01563
0519
Spd Loop Dmd Filt TC
Parameters::Motor Control::Spd Loop Settings
REAL
0.0
0.0 to 15.0
ms
ALWAYS
TECHNICIAN 4
01565
0520
Spd Loop Fbk Filt TC
Parameters::Motor Control::Spd Loop Settings
REAL
1.0
0.0 to 15.0
ms
ALWAYS
TECHNICIAN 4
01567
0521
Spd Loop Aux Torq Dmd
Parameters::Motor Control::Spd Loop Settings
REAL
0.00
-300.00 to 300.00
%
ALWAYS
TECHNICIAN 4
01569
0523
Spd Loop Adapt Thres
Parameters::Motor Control::Spd Loop Settings
REAL
0.00
0.00 to 10.00
%
ALWAYS
TECHNICIAN 4
01573
0524
Spd Loop Adapt Pgain
Parameters::Motor Control::Spd Loop Settings
REAL
20.00
0.00 to 300.00
ALWAYS
TECHNICIAN 4
01575
0525
Spd Demand Pos Lim
Parameters::Motor Control::Spd Loop Settings
REAL
110.00
-110.00 to 110.00
%
ALWAYS
TECHNICIAN 4
01577
0526
Spd Demand Neg Lim
Parameters::Motor Control::Spd Loop Settings
REAL
-110.00
-110.00 to 110.00
%
ALWAYS
TECHNICIAN 4
01579
0527
Sel Torq Ctrl Only
Parameters::Motor Control::Spd Loop Settings
BOOL
FALSE
ALWAYS
TECHNICIAN 4
01581
0528
Direct Input Select
Parameters::Motor Control::Spd Direct Input
USINT
(enum)
0
0:NONE
1:ANIN1
2:ANIN2
ALWAYS
TECHNICIAN 4
01583
0529
Direct Input Ratio
Parameters::Motor Control::Spd Direct Input
REAL
1.0000
-10.0000 to 10.0000
ALWAYS
TECHNICIAN 4
01585
0530
Direct Input Pos Lim
Parameters::Motor Control::Spd Direct Input
REAL
110.00
-110.00 to 110.00
%
ALWAYS
TECHNICIAN 4
01587
0531
Direct Input Neg Lim
Parameters::Motor Control::Spd Direct Input
REAL
-110.00
-110.00 to 110.00
%
ALWAYS
TECHNICIAN 4
01589
0533
Total Spd Demand RPM
Parameters::Motor Control::Spd Loop Diagnostics
REAL
x.xx
-30000.00 to 30000.00
RPM NEVER
TECHNICIAN 4
01593
0534
Total Spd Demand %
Parameters::Motor Control::Spd Loop Diagnostics
REAL
x.xx
-200.00 to 200.00
%
NEVER
TECHNICIAN 4
01595
0535
Speed Loop Error
Parameters::Motor Control::Spd Loop Diagnostics
REAL
x.xx
-400.00 to 400.00
%
NEVER
TECHNICIAN 4
01597
0536
Speed PI Output
Parameters::Motor Control::Spd Loop Diagnostics
REAL
x.xx
-500.00 to 500.00
%
NEVER
TECHNICIAN 4
01599
0555
PMAC Max Speed
Advanced Setup::Motor Control::Motor Data PMAC
Parameters::Motor Control::PMAC Motor Data
REAL
3000
0 to 30000
RPM ALWAYS
TECHNICIAN 4
01637
0556
PMAC Max Current
Same as PNO 555
REAL
4.50
0.00 to 5000.00
A
ALWAYS
TECHNICIAN 4
01639
0557
PMAC Rated Current
Same as PNO 555
REAL
4.50
0.00 to 5000.00
A
ALWAYS
TECHNICIAN 4
01641
Содержание AC30V Series
Страница 33: ...4 15 Installation AC30V series Variable Speed Drive Wiring Diagrams APPLICATION 0 BASIC SPEED CONTROL...
Страница 34: ...Installation 4 16 AC30V series Variable Speed Drive Basic Speed Control Wiring...
Страница 35: ...4 17 Installation AC30V series Variable Speed Drive APPLICATION 1 AUTO MANUAL CONTROL...
Страница 36: ...Installation 4 18 AC30V series Variable Speed Drive Auto Manual Control Wiring...
Страница 37: ...4 19 Installation AC30V series Variable Speed Drive APPLICATION 2 RAISE LOWER TRIM...
Страница 38: ...Installation 4 20 AC30V series Variable Speed Drive Raise Lower Trim Wiring...
Страница 39: ...4 21 Installation AC30V series Variable Speed Drive APPLICATION 3 PRESETS SPEEDS...
Страница 40: ...Installation 4 22 AC30V series Variable Speed Drive Presets Speeds Wiring...
Страница 41: ...4 23 Installation AC30V series Variable Speed Drive APPLICATION 4 PID CONTROL...
Страница 42: ...Installation 4 24 AC30V series Variable Speed Drive PID Control Wiring...
Страница 162: ...Sequencing Logic B 2 AC30V series Variable Speed Drive SEQUENCING DIAGRAM...
Страница 174: ...Compliance C 8 AC30V series Variable Speed Drive Conducted Emissions Profile Unfiltered Product Frame D Frame E Frame F...
Страница 277: ...D 80 Parameter Reference AC30V series Variable Speed Drive Setpoint Drive Frequency Frequency 1 Frequency 2...
Страница 325: ...E 2 E Plan Library AC30V series Variable Speed Drive Which then brings up the E Plan page...