6-1
Programming Your Application
650 Series AC Drive
1
P
ROGRAMMING
Y
OUR
A
PPLICATION
You can program the drive to your specific application. This programming simply involves
changing parameter values. For instance, parameter
P
1 selects various Applications which can
be used as starting points for application-specific programming.
Each Application internally re-wires the drive for a different use when it is loaded. The default
for the parameter is "1". Changing this parameter's setting to "2" will load Application 2. Refer
to Chapter 12: “Applications” for further information.
If necessary, there are three parameters for tuning your drive. Refer to PID - Tuning Your Drive,
page 6-8.
Saving Your Modifications
When parameter values are modified or an Application is loaded, the new settings are saved
automatically. The drive will retain the new settings during power-down.
MMI Parameters
This table provides information about each parameter accessible using the keypad, or MMI
(Man Machine Interface). For more information, refer to the 650 Software Product Manual on
our website: www.SSDdrives.com.
Key to MMI Parameters Table
F
Parameters indicated with
F
are visible with full menus only. Refer to the
DETAILED MENUS parameter (
ST
99).
M
Parameters indicated with
M
are Motor Parameters. They are not reset by changing
Application using parameter
P
1; all other parameters are reset to default values.
Note:
The “Range” for a parameter value is given in the Configurable Parameters Table.
Ranges for outputs are given as “—.xx %”, for example, indicating an indeterminate
integer for the value, to two decimal places.
MMI Parameters Table
MMI Parameters Table
Display
Parameter
Description
Range
Default
SET::PAR Menu
APPLICATION
This parameter selects and loads the Application to
be used. APP 0 will not control a motor. APP 6, 7,
8 & 9 are reserved for future use.
Refer to the 650 Software Product Manual,
Chapter 5: "Applications" which gives detailed
information about each Application.
Note:
Parameter values are changed to
factory settings by loading a new
Application, except Motor Parameters
(indicated
M
)
0= NULL
1= STANDARD
2= LOCAL/REM
(AUTO/MANUAL)
3= PRESETS
4= RAISE/LOWER
5= PID
6= APP 6
7= APP 7
8= APP 8
9= APP 9
1
MAX SPEED
M
The frequency at which the 650 will run when
maximum setpoint is applied. The default can be
either 50 or 60Hz.
7.5 to 300Hz
product
code
dependent
MIN SPEED
The minimum frequency at which the 650 will run,
as a percentage of the MAX SPEED parameter
-100.0 to 100.0%
0.0%
ACCEL TIME
M
The time taken for the 650 output frequency to
ramp up from zero to MAX SPEED
0.0 to 3000.0s
product
code
dependent
DECEL TIME
M
The time taken for the 650 output frequency to
ramp down from MAX SPEED to zero
0.0 to 3000.0s
product
code
dependent