Programming Your Application
650 Series AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
FIXED BOOST
M
VF
Used to correctly flux the motor at low speeds. This
allows the drive to produce greater starting torque
for high friction loads. It increases the motor volts
above the selected V/F characteristic at the lower
end of the speed range
OUTPUT VOLTS
FREQUENCY
f B
25%
100%
BOOST
f B
= BASE FREQUENCY
0%
INCREASING
INCREASED
TORQUE
CONSTANT
POWER RANGE
FLUXING
NORMAL FLUXING
0.00 to 25.00%
product
code
dependent
PASSWORD
A password may be set to prohibit unauthorised
adjustment of parameters. When
P
99 is set to
non-zero you will be required to match this value
before parameters can be adjusted
0000 – FFFF
0000
Parameters
P
301 to
P
308 are visible in the PAR menu when Application 3 is selected in parameter
P
1
PRESET 0
A user-adjustable speed preset, set by
potentiometer
-100.00 to 100.00
-
PRESET 1
A user-adjustable speed preset
-100.00 to 100.00
20.00
PRESET 2
A user-adjustable speed preset
-100.00 to 100.00
50.00
PRESET 3
A user-adjustable speed preset
-100.00 to 100.00
100.00
PRESET 4
A user-adjustable speed preset
-100.00 to 100.00
-10.00
PRESET 5
A user-adjustable speed preset
-100.00 to 100.00
-20.00
PRESET 6
A user-adjustable speed preset
-100.00 to 100.00
-50.00
PRESET 7
A user-adjustable speed preset
-100.00 to 100.00
-100.00
Parameters
P
401 to
P
404 are visible in the PAR menu when Application 4 is selected in parameter
P
1
R/L RAMP TIME
The time taken to ramp the Raise/Lower output
from 0.00% to 100.00% of its value
0.0 to 600.0s
10.0s
R/L MAX VALUE
The maximum value for the ramp output
-100.00 to 100.00% 100.00%
R/L MIN VALUE
The minimum value for the ramp output
-100.00 to 100.00% 0.00%
R/L RESET VALUE The value the output is set to when Reset is TRUE,
when DIN4 (terminal 10) is 24V in Application 4
-100.00 to 100.00% 0.00%
Parameters
P
501 and
P
506 are visible in the PAR menu when Application 5 is selected in parameter
P
1
PI P GAIN
The PI proportional gain
0.00 to 100.00
0.10
PI I GAIN
The PI integral gain
0.00 to 100.00
1.00
PID D GAIN
F
The PID derivative gain
0.00 to 100.00
0.00
PID D FILTER TC
F
In order to help attenuate high frequency noise on
the derivative term, a first order lag has been
provided. This parameter determines the filter time
constant.
0.05 to 10.00s
0.05s
PID FEEDBACK
GAIN
F
A multiplier applied to the feedback signal of the
PID
-10.00 to 10.00
1.00
PID LIMIT
F
Determines the maximum positive and negative
excursion (Limit) of the PID output
0.00 to 300.00%
300.00%
PID SCALING
F
This parameter represents an overall scaling factor
which is applied after the PID positive and negative
limit clamps
-3.0000 to 3.0000
1.0000