Programming Your Application
6-5
590 Series DC Digital Converter
ANALOG INPUTS
The analog input block is used to scale
and clamp the inputs for terminals A2 to
A6.
Note:
ANIN 2 (A3) is not reconfigurable and is connected directly to the SETUP PARAMETERS::
SPEED LOOP:: SETPOINTS:: RATIO 2 (A3) input, and the SETUP PARAMETER:: CURRENT
LOOP:: I DMD. ISOLATE switch. Refer to Chapter 15: The Default Application” block
diagram for more information.
Tag 493 allows access to the calibrated value of ANIN 2 (via an internal link for
example). To avoid interference with other drive functions the parameter RATIO 2 (A3)
must be set to zero, and the I DMD. ISOLATE parameter must be set to DISABLED, i.e.
selecting the Speed Loop as shown in the main block diagram.
ANIN 2 (A3) is a direct input into the speed loop/current loop and is scanned
synchronously with the current loop (typically every 3.33ms) rather than every micro cycle
time (typically 7ms). Therefore it should be used for any signal whose response is critical
e.g. a trim input from a digital speed and position locking system.
ANIN 1 (A2)
–
OUTPUT [246]
–
100
1.0000
–
[230] CALIBRATION
–
100.00 %
–
[231] MAX VALUE
–
-100.00 %
–
[232] MIN VALUE
–
–
ANIN 1 (A2)
–
0.00V
ANIN 3 (A4)
–
OUTPUT [249]
–
5
1.0000
–
[236] CALIBRATION
–
100.00 %
–
[237] MAX VALUE
–
-100.00 %
–
[238] MIN VALUE
–
–
ANIN 3 (A4)
–
0.00V
ANIN 2 (A3)
1.0000
–
[233] CALIBRATION
–
100.00 %
–
[234] MAX VALUE
–
-100.00 %
–
[235] MIN VALUE
–
–
ANIN 2 (A3)
–
0.00V
ANIN 4 (A5)
–
OUTPUT [250]
–
48
1.0000
–
[239] CALIBRATION
–
100.00 %
–
[240] MAX VALUE
–
-100.00 %
–
[238] MIN VALUE
–
–
ANIN 4 (A5)
–
0.00V
ANIN 5 (A6)
–
OUTPUT [247]
–
301
1.0000
–
[242] CALIBRATION
–
100.00 %
–
[243] MAX VALUE
–
-100.00 %
–
[244] MIN VALUE
–
–
ANIN 5 (A6)
–
0.00V
MMI Menu Map
1
SYSTEM
2
CONFIGURE I/O
3
ANALOG INPUTS
4
ANIN 1 (A2)
4
ANIN 2 (A3)
4
ANIN 3 (A4)
4
ANIN 4 (A5)
4
ANIN 5 (A6)
CALIBRATION
MAX
VALUE
MIN
VALUE
DESTINATION
TAG
Parameter Descriptions
CALIBRATION
Range: -3.0000 to 3.0000
The analog input scaling ratio.
MAX VALUE
Range: -300.00 to 300.00
The maximum value of the scaled analog input.
MIN VALUE
Range: -300.00 to 300.00
The minimum value of the scaled analog input
ANIN 1 (A2) to ANIN 5 (A6)
Refer to the DIAGNOSTICS function block description, page 6-18.
OUTPUT
Range: 0 to 499
(DESTINATION TAG)
The destination Tag No. of the scaled analog input value.
Содержание 590 series
Страница 12: ...605 Frequency Inverter HA389591 Issue 1 Contents Contents Page Cont 12...
Страница 16: ...1 4 Getting Started 590 Series Digital Converter...
Страница 22: ...2 6...
Страница 43: ...Installing the Converter 3 21 590D DC Digital Converter HA467078 Figure 3 6 110A 150A Stack Assembly...
Страница 44: ...3 22 Installing the Converter 590D DC Digital Converter HA467078 Figure 3 7 180A Stack Assembly...
Страница 45: ...Installing the Converter 3 23 590D DC Digital Converter HA467078 Figure 3 8 270A Stack Assembly...
Страница 46: ...3 24 Installing the Converter 590D DC Digital Converter HA467078 Figure 3 9 360A Stack Assembly...
Страница 47: ...Installing the Converter 3 25 590D DC Digital Converter HA467078 Figure 3 10 450A Stack Assembly...
Страница 48: ...3 26 Installing the Converter 590D DC Digital Converter HA467078 Figure 3 11 720A Stack Outline Drawing...
Страница 49: ...Installing the Converter 3 27 590D DC Digital Converter HA467078 Figure 3 12 720A Stack Outline Drawing...
Страница 64: ...3 42 Installing the Converter 590D DC Digital Converter HA467078...
Страница 82: ...4 18 Operating the Converter 590 Series DC Digital Converter...
Страница 90: ...5 8 The Man Machine Interface MMI 590 Series DC Digital Converter...
Страница 168: ...9 6 Control Loops 590 Series DC Digital Converter...
Страница 222: ...13 14 Standard and Optional Equipment 590 Series DC Digital Converter...
Страница 234: ...15 2 The Default Application 590 Series DC Digital Converter...
Страница 242: ......