Operating the Converter
4-7
590 Series DC Digital Converter
If the field voltage is not correct, make the following checks:
9
.1
Internally Supplied Field:
•
Check that 3-phase is applied to terminals L1, L2 and L3 when
the main contactor
is closed.
•
Check that the 3 coding fuses on the power board are
healthy.
•
The FIELD ENABLE parameter should be set to
ENABLE.
•
With the FIELD ENABLE parameter in view, press the
↓
(DOWN) key. The
display changes to FLD CTRL MODE IS. Press the
M
key. Is this set to
VOLTAGE CONTROL or CURRENT CONTROL?
If set to VOLTAGE CONTROL, check the value
of the RATIO OUT/IN parameter. This should be
set to 90% maximum.
If set to CURRENT CONTROL, check the field
current calibration set-up, refer back to
“Calibration”.
If the
field volts
are
at maximum,
check
the
field continuity. (The
field current may initially be lower than the
rated value due to a
cold field.)
9.2
Externally Supplied Field:
•
Check the voltage applied (externally fused) to terminals D1 and D2.
•
Check the phasing
of voltage applied
to D1
and D2:
D1 must
be connected directly or
indirectly to
the Red phase
on main
power
terminal L1.
D2
must be connected directly
or indirectly to
the
Yellow phase on main power terminal L2.
•
The FIELD ENABLE should be set to ENABLE.
•
With the FIELD ENABLE parameter in view, press the
↓
(DOWN) key. The display changes to FLD CTRL MODE
IS. Press the
M
key. Is this set to VOLTAGE CONTROL
or CURRENT CONTROL?
If set to VOLTAGE CONTROL, check the value
of the RATIO OUT/IN parameter. This should be set
to 90% maximum.
If set to CURRENT CONTROL, check the field current calibration set-up,
refer back to “Calibration”.
Check that 3-phase is applied to terminals L1, L2 and L3.
10
Check that all six MMI LEDs are now illuminated.
Note that any
external interlocks
which affect the Enable input C5 will affect the state
of
the RUN LED.
11
If the STANDSTILL LOGIC parameter in the STANDSTILL menu at level 2 is
ENABLED, temporarily set it to DISABLED.
MMI Menu Map
1
SETUP PARAMETERS
2
FIELD CONTROL
FIELD
ENABLE
MMI Menu Map
1
SETUP PARAMETERS
2
FIELD CONTROL
3
FLD VOLTAGE VARS
RATIO
OUT/IN
MMI Menu Map
1
SETUP PARAMETERS
2
FIELD CONTROL
FIELD
ENABLE
MMI Menu Map
1
SETUP PARAMETERS
2
FIELD CONTROL
3
FLD VOLTAGE VARS
RATIO
OUT/IN
MMI Menu Map
1
SETUP PARAMETERS
2
STANDSTILL
STANDSTILL
LOGIC
Содержание 590 series
Страница 12: ...605 Frequency Inverter HA389591 Issue 1 Contents Contents Page Cont 12...
Страница 16: ...1 4 Getting Started 590 Series Digital Converter...
Страница 22: ...2 6...
Страница 43: ...Installing the Converter 3 21 590D DC Digital Converter HA467078 Figure 3 6 110A 150A Stack Assembly...
Страница 44: ...3 22 Installing the Converter 590D DC Digital Converter HA467078 Figure 3 7 180A Stack Assembly...
Страница 45: ...Installing the Converter 3 23 590D DC Digital Converter HA467078 Figure 3 8 270A Stack Assembly...
Страница 46: ...3 24 Installing the Converter 590D DC Digital Converter HA467078 Figure 3 9 360A Stack Assembly...
Страница 47: ...Installing the Converter 3 25 590D DC Digital Converter HA467078 Figure 3 10 450A Stack Assembly...
Страница 48: ...3 26 Installing the Converter 590D DC Digital Converter HA467078 Figure 3 11 720A Stack Outline Drawing...
Страница 49: ...Installing the Converter 3 27 590D DC Digital Converter HA467078 Figure 3 12 720A Stack Outline Drawing...
Страница 64: ...3 42 Installing the Converter 590D DC Digital Converter HA467078...
Страница 82: ...4 18 Operating the Converter 590 Series DC Digital Converter...
Страница 90: ...5 8 The Man Machine Interface MMI 590 Series DC Digital Converter...
Страница 168: ...9 6 Control Loops 590 Series DC Digital Converter...
Страница 222: ...13 14 Standard and Optional Equipment 590 Series DC Digital Converter...
Страница 234: ...15 2 The Default Application 590 Series DC Digital Converter...
Страница 242: ......