Technical Specifications
11-3
590 Series DC Digital Converter
Internal
Fuses
PCB Fuses
Board Identification
Fuse
Rating
Parker SSD Drives
Part Number
AH385851
FS1, 5x20mm glass slow-blow (for auxiliary supply,
contactor, fan supply)
3A CH540033
AH385621
FS1, 5x20mm glass slow-blow (for auxiliary supply,
contactor, fan supply)
3A CH540033
AH385128
FS1, 5x20mm glass (fan supply)
FS2, 5x20mm glass (contactor)
FS3, 5x20mm glass slow-blow (auxiliary supply)
1A
3A
400mA
CH460013
CH460033
CH540042
Field Fuses
Identification
Fuse Rating
Parker SSD Drives
Part Number
10x38mm (all units up to 270A output current)
10A
CH430014
10x38mm (all units above 270A output current)
20A
CH430024
External Fuses (European)
For fuses where compliance to UL Standards are required, refer to Chapter 12: “Installing the
Converter” - Requirements for UL Compliance.
Product Code
BS88 Type Fuse
DIN Type Fuse
Thyristor A
2
t
Block 2
Fuse Rating
Parker SSD Drives
Part Number
Fuse Rating
Part Number
@ 125
o
C Junction
Temperature
0010 to 0350
35A
CH110353
40A
CH570044
800 A
2
t
0351 to 0700
75A
CH120753
80A
CH570084
8,000 A
2
t
0701 to 1100
110A
CH120114
160A
CH580164
8,000 A
2
t
1101 to 1800
150A
CH120154
200A
CH580025
15,000 A
2
t
1801 to 2700
300A
CH130035
550A
CH590554
125,000 A
2
t
2701 to 4500
---
---
700A
CH590075
320,000 A
2
t
4501 to 7200
---
---
800A
CH590085
500,000 A
2
t
Earthing/Safety
Details
Earthing
Permanent earthing is mandatory on all units because the earth leakage current exceeds 3.5mA
ac/10mA dc under normal operating conditions. Permanent earthing can be laid in two ways::
1.
By using a copper conductor of at least 10mm² cross-sectional area.
2.
By using a second conductor, through separate terminals electrically parallel to the
protective conductor.
Note:
Each conductor itself must meet the local requirements for a protective earth
conductor.
Input Supply Details
(TN) and (IT)
Units with or without external filters are suitable for use on earth referenced (TN) supplies, but
units used with a filter are not recommended for non-earth referenced (IT) supplies..
Earth Leakage Current
>50mA (all models)
Содержание 590 series
Страница 12: ...605 Frequency Inverter HA389591 Issue 1 Contents Contents Page Cont 12...
Страница 16: ...1 4 Getting Started 590 Series Digital Converter...
Страница 22: ...2 6...
Страница 43: ...Installing the Converter 3 21 590D DC Digital Converter HA467078 Figure 3 6 110A 150A Stack Assembly...
Страница 44: ...3 22 Installing the Converter 590D DC Digital Converter HA467078 Figure 3 7 180A Stack Assembly...
Страница 45: ...Installing the Converter 3 23 590D DC Digital Converter HA467078 Figure 3 8 270A Stack Assembly...
Страница 46: ...3 24 Installing the Converter 590D DC Digital Converter HA467078 Figure 3 9 360A Stack Assembly...
Страница 47: ...Installing the Converter 3 25 590D DC Digital Converter HA467078 Figure 3 10 450A Stack Assembly...
Страница 48: ...3 26 Installing the Converter 590D DC Digital Converter HA467078 Figure 3 11 720A Stack Outline Drawing...
Страница 49: ...Installing the Converter 3 27 590D DC Digital Converter HA467078 Figure 3 12 720A Stack Outline Drawing...
Страница 64: ...3 42 Installing the Converter 590D DC Digital Converter HA467078...
Страница 82: ...4 18 Operating the Converter 590 Series DC Digital Converter...
Страница 90: ...5 8 The Man Machine Interface MMI 590 Series DC Digital Converter...
Страница 168: ...9 6 Control Loops 590 Series DC Digital Converter...
Страница 222: ...13 14 Standard and Optional Equipment 590 Series DC Digital Converter...
Страница 234: ...15 2 The Default Application 590 Series DC Digital Converter...
Страница 242: ......