English
5 / 14
ATT140-340
5.3 Screens displayed
5.3.1 Main Screen
Shows
Alarm code
Unit Status
OFF
: Off
ON
: On
OF RMT
: Off by remote contact
OF CMP: Off by remote contact
Temperature of
Dew point
or
Temperature
Inlet Absorber
(operating in sum-
mer)
Level indicator
of Dewpoint
temperature
Date / hour
Shows bypass (operating only with Winter /
Summer enabled)
Bypass close
Bypass open
5.3.2 USER PARAMETER
Press the key Prg and enter on
MAIN MENU
- - -Main Menu - - -
START/STOP
USER SETTINGS
SERVICE
INFORMATION
Select
USER SETTINGS,
press
Enter
to confi rm
.
Shows the “user setting menu”:
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
Select
DRYER SETTINGS
press
Enter
to confi rm. This Screen appears
U1 - DEWP.SET (°C): -40
U2 - PRESSURE (barg): 07
U3 - MODE: Forced Rig.
U4 - ALARM RELAY MODE:
by: ALARMS & WARNINGS
U6 - DPM: NO FITTED
AUTOMATIC PRESSURE
U17 - MODE: MANUAL
U18 - READ P.: 00 bar
AUTOMATIC BY-PASS
U15 - BY-PASS MODE:
MANUAL
DEW POINT AUTOMATIC
U20 - MODE: MANUAL
With the keys
Up
,
Down
and
Enter
you can select/change a parameter:
U1 - SET of Dew Point
U2 - Work pressure [barg]
U3 - Working Mode: Forced Rig. O Normal
U4 - Alarm Relay Mode by: alarms&warnings or allarms.
U6 - DPM: Fitted o No Fitted - with the control fo the dew point (Fitted)
or with fi xed time (No Fitted)
U15 - By-pass. mode (automatic/manual)
U17 - Pressure: mode (automatic/manual)
U18 - Pressure
U20 - Dew point: mode (automatic/manual)
When you change the parameter press
Enter
to confi rm.
Press
Esc
to return on
USER SETTINGS MENU
.
Select
DATE
for change the date and the time:
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
This Screen appears:
2011/Oct/24 15.49
Change: NO
M10
Press esc to return on
USER SETTINGS MENU
.
Select
BMS
:
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
This Screen appears:
- BMS -
U7 - ADRESS: 001
U8 - BAUDRATE: 9600
The parameters
U7
and
U8
selects the adress fo the supervision.
Press esc to return on the
USER SETTINGS MENU
.
Select
MOISTURE DRAIN:
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
This Screen appears:
- MOISTURE DRAIN -
U9 - MODE: Continue
U10 - TIMED On (s):
U11 - TIMED Off (s): 1
U9 - Mode condensate drain (continue; timed; capacitive);
U10 - Time “ON” with timed condensate drain;
U11 - Time “OFF” with timed condensate drain;
Press
Esc
to return on
USER SETTINGS MENU
.
Select
OTHER
:
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
This Screen appears:
U12 - BACKLIGHT ON: NO
U13 - Enable Money : NO
U14 - Money : Euro
U15 - Money / KWh : 0.120
U16 - Saving Compared
to Heatless
U2
5.3.3 SERVICE PARAMETER
On
MAIN MENU
select
Service
and press
Enter
to confi rm.
- - -Main Menu - - -
START/STOP
USER SETTINGS
SERVICE
INFORMATION
This Screen appears with the request of a password.
INSERT PASSWORD
000
These confi guration parameters must not be editable by the customer.
5.3.4 INFORMATIONS
On
MAIN MENU
select
INFORMATION
and press
Enter
to confi rm.
Содержание ATT140