English
3 / 14
ATT140-340
4 Commissioning
4.1 Preliminary checks
Before starting the dryer, make sure:
• installation was carried out according that given in the section 9.2;
• the air inlet valves are closed and that there is no air fl ow through
the dryer;
• the power supply is correct.
4.2 Starting
Before starting the dryer follow the following instruction:
• Switch the power on by turning the MAIN SWITCH (IG)
&
to “
ON”.
• the crankcase heater will now start heating
!Y
THE CRANKCASE HEATER MUST BE SWITCHED ON 12
HOURS BEFORE STARTING THE DRYER.
Failure to comply with this rule may cause serious damage to the com-
pressor.
• Shows the “MAIN SCREEN VIEW on display.
Start the air compressor.
Start-up procedure dryer:
Press
to enter on “Main Menu”
- - -Main Menu - - -
START/STOP
USER SETTINGS
SERVICE
INFORMATION
Select
START/STOP
and confi rm with
Enter
- - -Main Menu - - -
START/STOP
USER SETTINGS
SERVICE
INFORMATION
Select:
NORMAL START/STOP
and confi rm with
Enter
- On/Off Menu -
NORMAL START/STOP
STOP DIRECTLY
Confi rm
START
, for the start-up
ENABLE UNIT RUNNING
STOP
“Compressed Inlet Air” pressure
insuffi cient, dryer blocked.
INSUFFICIENT AIR PRESSURE
!Y
Attention: The air compressor must be started before the
dryer. Otherwise you may damage the electric resistance.
The fi rst start-up is in “Forced Regeneration” on default.
The unit works for a complete cycle (2 columns), after switches to normal
working.
Y
It is recommended to complete this type of starting with the air out-
let valve closed, to preserve the correct operation of the desiccant bed.
4.3 Operation
Leave the dryer in working during the period of working of the air com-
pressor.
• The dryer works automatically, calibrations are not required on the
fi eld;
• if there are excessive and unexpected air fl ows, by-pass to avoid
overloading the dryer.
4.4 Operation with Dew point control
In the case of work loads below the nominal or if you want different dew
point of -40 ° C, it is possible to work in
Dew Point Control
. The system
automatically controls the time of the cycles of operation to obtain and
maintain the predetermined dew point, with the result of energy saving in
case of work with partial loads.
Procedure to set “dew point control”.
Press Prg to enter on main menu
Using
Up
and
Down
select
“
USER SETTINGS”
Press
Enter
to confi rm.
- - -Main Menu - - -
START/STOP
USER SETTINGS
SERVICE
INFORMATION
Shows the “User settings menu
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
Using
Up
and
Down
select
“DRYER SETTINGS”
Press
Enter
to confi rm.
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
Using
Up
and
Down
select
the parameter.
Press
Enter
to confi rm..
U1 - DEWP.SET (°C): -40
U2 - PRESSURE (barg): 07
U3 - MODE: Forced Rig.
U4 - ALARM RELAY MODE:
by: ALARMS & WARNINGS
U6 - DPM: NO FITTED
Select the parameter
U1- DEWP.SET
(°C) and set the value you need.
Press
Enter
to confi rm. see Table 1 for identifying the correct value
to be set
Select the parameter
U6- DPM
: set the mode
FITTED.
Press
Enter
to confi rm.
Table 1
Dew
Point
Application
-70°C
Request for a very low dew point.
-40°C
Request for a very low dew point.
(depend on the type of the process.).
-20°C
Request for a low dew point.
When the pipes air compressed are in external environ-
ment and the minimum winter ambient temperatures are
above -10 to -15 ° C.
-10°C
Request for a low dew point.
When the pipes air compressed are in external environ-
ment and the minimum winter ambient temperatures are
above -5°C.
0°C
Request for a dew point standard.
When the pipes air compressed are in external environ-
ment and the minimum winter ambient temperatures are
above 10°C.
Important: for correct readings, the Dew point sensor must work at
a precise air fl ow, which is adjusted by a fl ow meter (no. 33).
CORRECT CALIBRATION: LEVEL 2 ÷ 5 liters/minutes
To ensure optimal Dew point sensor operation, comply with the
maintenance instructions given in para. 6.4.
In this regard, the sensor connection is fi tted with a shut-off valve to