Command Descriptions
317
TSCF
Transfer Controller Status (full-text report)
Type
Transfer
Syntax
<a_><!>TSCF
Units
n/a
Range
n/a
Default
n/a
Response
TSCF: (see
example
below)
See Also
[ SC ], SCANP, TSC
Product Rev
GT6K 6.0
GV6K 6.0
The
TSCF
command provides a full-text report of the current “Controller Status” register. This is an
alternative to the binary report (
TSC
).
Example
TSCF
response:
*TSCF
*Reserved NO Reserved NO
*Reserved NO Reserved NO
*SCANP Running NO Reserved NO
*Reserved NO Reserved NO
*
*Reserved NO Reserved NO
*Reserved NO Reserved NO
*Reserved NO Reserved NO
*Reserved NO Reserved NO
*
*Reserved NO Reserved NO
*Reserved NO Reserved NO
*Reserved NO Reserved NO
*Reserved NO Reserved NO
*
*Reserved NO Reserved NO
*Reserved NO Reserved NO
*Reserved NO Reserved NO
*Reserved NO Reserved NO
TSCAN
Transfer Scan Time of PLCP Program
Type
Transfer; PLC Scan Program
Syntax
<a_><!>TSCAN
Units
Response is in increments of 2 milliseconds
Range
2 ms - unlimited
Default
n/a
Response
TSCAN
*TSCAN4 (4 ms corresponds to 2 system updates)
See Also
EXE, PLCP, SCANP
Product Rev
GT6K 6.0
GV6K 6.0
The
TSCAN
command reports the duration it takes the last PLCP program to be scanned completely. A
compiled PLCP program is launched into Scan mode using the
SCANP
command. During each 2 ms system
update, the PLCP program is scanned an allotted 0.5 ms window. If the PLCP program requires more than
0.5 ms to be scanned, the program will be paused and then resumed at the next system update. The value
reported by the
TSCAN
command is in multiples of the 2 ms system update period.
Example:
SCANP PLCP1
; Start execution of compiled PLCP program PLCP1 in Scan mode
TSCAN
; Report the duration of the scan program in multiples of the
; 2 millisecond system update period. An example response might
; be *TSCAN4 (indicates that 2 system update periods, a total of
; 4 milliseconds was required to scan the last PLCP program).