18
Reference & Installation Manual
•
During the Intellizone Delay, a second zone has caused an
alarm.
•
During the Intellizone Delay, the zone in alarm has restored
(closed) and re-occurred (opened).
•
The zone in alarm is still open after the Intellizone Delay has
elapsed.
This feature is not for use in UL installations.
Intellizone Delay Timer
Section [065]: 010 to 255 seconds; Default = 45 seconds
Enter the desired 3-digit value into section [065] to program
the Intellizone Delay Timer.
Delay Before Alarm Report Code Transmission
Sections [001] to [032]: Zones 1 to 32; option [7]
Option [7] OFF = Delay alarm transmission disabled (default)
Option [7] ON =
Delay alarm transmission enabled
This feature is commonly used with Entry Delay zones to reduce
false alarms created by new users who may not disarm the
system in time. This feature works as follows:
•
When an alarm condition occurs on a zone with this option
enabled, the console enables the bell/siren output, but does
not report the alarm to the monitoring station until the end of
the Alarm Transmission Delay.
•
During this period, disarming the system disables the bell/
siren output and cancels the report code transmission.
This feature is not for use in UL installations.
Alarm Transmission Delay
Section [075]: 001 to 255 seconds; 000 = Disabled; Default
= 0 seconds
Enter the desired 3-digit delay value into section [075] to
program the Alarm Transmission Delay.
Force Zones
Sections [001] to [032]: Zones 1 to 32; Option [8]
Option [8] OFF = Force zone disabled
Option [8] ON =
Selected zone is Force enabled (default)
Any open Force zones at the time of arming will be considered
deactivated by the console. If during this period a deactivated
zone is closed, the console will revert that zone to active status.
Consequently, the console will generate an alarm if the zone is
breached.
Fire zones cannot be programmed with the Force zone
option because the console will not bypass a Fire zone when
the system is being Force armed.
This feature is not for use in UL installations.
Stay Delay Zones
Section [094]: Options [1]
Option [1] OFF = Stay Delay zone disabled (default)
Option [1] ON =
Stay Delay zone enabled
When a Follow/Stay or Instant/Stay zone is armed using the Stay
or Instant arming methods, with this option enabled and the zone
is triggered, an alarm will not generate until the programmed
Stay Delay elapses. A zone defined as Stay Delay follows the
Entry Delay 1 Timer. To program the Entry Delay Timers, refer to
Entry Delay 1 on page 15.
This feature is not for use in UL installations.
Zones 31 and 32 Become Hardwire Zones
Section [095]: Options [1] and [2]
Option [1] OFF = Wireless zone 31 remains unchanged (default)
Option [1] ON =
Wireless zone 31 uses the on-board hardwire
zone input 1
Option [2] OFF = Wireless zone 32 remains unchanged (default)
Option [2] ON =
Wireless zone 32 uses the on-board hardwire
zone input 2
The Magellan console comes with two on-board zone inputs,
hardwire zone inputs 1 and 2. Section [095] options [1] and [2]
allow you to convert zones 31 and 32 from wireless to hardwire
by allowing you to connect hardwire detection devices (i.e., door
contacts) to zone inputs 1 and 2.
•
With section [095] option [1] ON, zone 31 is connected to
zone input 1.
•
With section [095] option [2] ON, zone 32 is connected to
zone input 2.
EOL (End-Of-Line) Zones
Section [095]: Option [3]
Option [3] OFF = Hardwire zones 1 & 2 do not require EOL
resistors (default)
Option [3] ON =
Hardwire zones 1 & 2 require EOL resistors
This feature only applies to Magellan’s on-board zone
inputs. Section [095] options [1] and/or [2] (see Zones 31
and 32 Become Hardwire Zones on page 18) must be ON in
order to use this feature.
If the hardwire detection devices connected to Magellan’s zone
inputs 1 and 2 have input terminals that require 1K
9
end-of-line
resistors, enable (ON) section [095] option [3]. For details on
using EOL resistors, refer to page 9.
When hardwired zones are used, the EOL Resistor Option must
be enabled for UL installations.
Wireless Programming
The Magellan system supports up to 32 wireless zones
and two wireless doorbells. These wireless zones are monitored
using transmitters such as wireless detectors and door contacts.
The Magellan console only supports the Paradox Magellan
series of wireless transmitters. The programming of the
transmitters is accomplished in two steps:
1. Assign the wireless transmitter to Magellan.
2. Program the wireless zone.
Содержание MG-6130
Страница 2: ......