4
Installation
keypads and other accessories in your security system. Their combined current consumption
(see Table 1) on each auxiliary output should not exceed 1A. The auxiliary supply is
microprocessor-protected against current overload and automatically shuts down if the
current exceeds 1.1A. Auxiliary power will resume once the overload condition has restored
and within 1-60 seconds after performing the dynamic battery test (see below).
2.3.4 Battery Test
The control panel conducts a dynamic battery test under load every 60 seconds. If the battery
is disconnected, or its capacity is too low, the [1] key in the trouble display mode will be on.
Key [1] also comes "on" if the battery voltage drops to 10.5 volts or less when the control
panel is running on the back-up battery (no AC). At 8.5 volts, the panel shuts down and all
outputs close.
2.3.5 Keypad Function Test
We recommend conducting a "power-up" test on keypads installed far from the control panel.
To do so temporarily connect the keypads near the control panel and connect the transformer.
After 10 seconds, begin entering random commands on the keypad and verify that the
keypad "beeps" in response to these commands. Then open a zone to ensure that the
keypad and the control panel are responding to these signals. If the keypad does not respond
and indicator lights do not illuminate, verify that approximately 16V
AC
is present at the "AC"
terminals. If AC is present, check the keypad wiring and verify there isn't a short between the
"black" and "red" keypad wires. If the keypad does not respond, please contact your local
Paradox Distributor.
2.4
Telephone Line Connection
Connect the incoming telephone company wires into the
TIP
and
RING
connections of the control panel. Then run the wires
from
T
-
1
and
R
-
1
to the telephone system as shown in figure 4.
Table 1 - Current Consumption
Motion Detectors
10-50mA typ.
636/646 Keypads
15mA DC typ.
(see detector instructions for details)
30mA DC max.
708 Comm. Module
35mA DC typ.
642 LCD Keypads
40mA DC typ.
75mA DC max.
55mA DC max.
SRI-18
46mA DC typ
135mA DC max.