Keypad zone supervision

Keypad 1 zone supervision

(Kpd 1)

Keypad 2 zone supervision

(Kpd 2)

(Address 210, key [11])

(Address 210, key [12])

ON

” = enabled

OFF

” = disabled

ON

” = enabled

OFF

” = disabled

Keypad zone supervision allows the system to verify the presence of a keypad and its keypad zone(s).
When enabled, only two keypad zones (one configured as keypad 1, and one configured as keypad 2)
can be used at one time. Any other keypad zone terminals must be shorted.

If using a 616, 626, or 633 LED keypad with software version 3.9 or earlier, OR a PS1 version 1.1, OR a
639/640 keypad with its keypad zone supervision feature disabled (address 32, key [3] “off”), or if the key-
pad zone is not used:

•  

KEYPAD ZONE SUPERVISION FEATURE MUST BE

OFF

”.

If using a 616, 626, or 633 LED keypad with software version 4.0 onward, OR a PS1 version 2.0 onward,
OR a 639/640 LCD keypad with its keypad zone supervision enabled (address 32, key [3] “on”):

KEYPAD ZONE SUPERVISION FEATURE MUST BE

ON

”.

Related features: Keypad connections. p.8

Zone Definition

(Addresses 212-242)

Zone definition is assigned during "feature selection" programming. Turning zone key "on" or "off" at
addresses 212-242 assigns a particular definition to the zone. (See Programming Work Sheets.)

Intelli zone

definition

(Addresses 212, 214)

Key “ON”:  An alarm will be generated and communicated following any two detections in zones
assigned this definition, whether the two detections stem from a single intellizone or any two separate
intellizones - as long as the two detections take place within a designated time frame. An alarm will also
be generated and communicated if an intellizone stays “open” for the total length of the designated “intel-
lizone” delay. The "intellizone" delay, which determines the period of time (between 16-256 seconds) in
which two detections must take place or an intellizone must remain open, is programmed at address 059.
"Intellizone" definition is disregarded while the panel is in audible alarm.

Key "OFF":  An alarm is generated as soon as the zone is opened. This feature should be disabled on UL
listed systems.

Silent/audible

(Addresses 216, 218)

Silent zones (keys "on") report alarms without triggering bells/sirens. (Reminder: fire zone is never silent.)
Audible zones (keys "off ") will trigger a bell or siren upon alarm generation. 

24 hour - fire/regular

(Addresses 220, 222)

"24 hour" zones (keys "on") generate alarms whenever the zone is detected, even if the system is not
armed. Zone 3 becomes a fire zone when defined "24 hour". The fire zone should always be connected
with a 1K

W

EOL resistor. If there is a line short in the fire zone, a fire alarm will be generated. If the line is

"open", a fire trouble report (if assigned at address 182) will be sent to the central, and trouble indicator
[11] and fire zone key [3] will flash on the keypad. Alarms in a fire zone generate an intermittent output
signal, regardless of system arming status. 

Instant

(Addresses 224, 226)

"Instant" zones (key "on") will immediately generate an alarm when detected while the system is armed.
There is no entry delay. 

Follow

(Addresses 228, 230)

"Follow" zones (key "on") are "instant" zones that switch to "delay" definition during entry delay.

IM728-738

21

728 (no ATZ):    Kpd 1 = Zone 5  Kpd 2 = Zone 6

738 (no ATZ):    Kpd 1 = Zone 7    Kpd 2 = Zone 8

728 (with ATZ): Kpd 1 = Zone 9  Kpd 2 = Zone 10

738 (with ATZ): Kpd 1 = Zone 13  Kpd 2 = Zone 14

Содержание Esprit 728

Страница 1: ...Installation Manual P R D O X S E C U R I T Y S Y S T E M S ESPRIT 728 738 IM728 738 960716 0000 VERSION 2 20 LISTED...

Страница 2: ...IRE ALARM application refer to NFPA Standard 74 for details on locating smoke detectors There must be at least one UL Listed Indoor Fire Alarm Warning Signaling Appliance 3 For U L Burglar Application...

Страница 3: ...unicator 6 Espload 6 Accessory Modules 6 Keypads 6 Current Consumption 6 BASIC INSTALLATION 6 11 LOCATION AND MOUNTING 6 EARTH GROUND 7 AC 7 PROGRAMMABLE OUTPUTS 7 BELL SIREN OUTPUT 7 AUXILIARY POWER...

Страница 4: ...g 17 Silent alarm 17 18 Dialing pulse rates 18 Reporting options 18 Bell squawk 18 Auto zone shutdown 19 Automatic event buffer transmission 19 Enable keypad panic signals 19 Keypad panic options 19 O...

Страница 5: ...rming 25 Fast Exit 25 System Disarming 25 Alarm Memory 25 SYSTEM PARTITIONING 25 26 Partitioning 25 Arming Disarming 26 Keyswitch push button arming disarming PS1 26 ZONE BYPASSING 27 Bypass Recall 27...

Страница 6: ...are identical This total compatibility significantly reduces the time required to conduct training programming and system upgrades There s just one set of procedures for all Esprit panels User friend...

Страница 7: ...8 728 10 zones 4 onboard zones 4 ATZ zones 2 keypad zones 738 14 zones 6 onboard zones 6 ATZ zones 2 keypad zones 616 626 633 LED keypads See Keypad Connections page 8 728 9 zones 4 onboard zones 4 A...

Страница 8: ...keypads 639 and 640 LCD keypads PS1 bedside remote For UL sys tems use only 616 626 640 or PS1 Current Consumption measured with battery connected without AC and with 1KW resistor on bell and 1KW resi...

Страница 9: ...ed by the Bell Bell terminals The bell output is micro processor controlled and will automatically shut down if current exceeds 3 amps The processor will allow current to resume as soon as another ala...

Страница 10: ...CD keypads 616 626 633 LED keypads To disable the keypad zone when keypad zone supervision is deactivated you must connect a 1KW resistor across the two connections labeled zone and com on the keypad...

Страница 11: ...10 key 8 on Tamper fault transmits separate code TAMPER WIRE FAULT DEFINITIONS AND OPTIONS When using 2 zone resistors the panel offers four possible definitions for tamper wiring recognition independ...

Страница 12: ...d To do so connect the negative side of smoke detector power to PGM1 PGM1 should then be programmed Timed N C normally closed pro grammed to open when any two keys on the keypad are pressed simultaneo...

Страница 13: ...nate If programmed a trouble report code will also be sent to the central station At 8 5 volts all outputs are closed ESPLOAD Esprit control panels can be remotely programmed with Espload upload downl...

Страница 14: ...o be programmed to contain 4 digits address 208 9 on Create a new installer code by entering the values of 1st and 2nd digit at address 005 3rd and 4th digit at address 006 and 5th and 6th digit at ad...

Страница 15: ...in a partitioned system If partitioning is deactivated the same value should be pro grammed for both account numbers To program account codes for System A and B press ENTER installer code 2 7 10 6 The...

Страница 16: ...conds Panic 2 Panic alarm will be reported to the central if keys 4 and 6 are pressed for 2 seconds Panic 3 Panic alarm will be reported to the central if keys 7 and 9 are pressed for 2 seconds Partia...

Страница 17: ...O Solid state switch conducts to negative 50mA upon an event or events and returns to its original state N O once the conditions that triggered it have terminated Regular N C Solid state switch opens...

Страница 18: ...ndicate which user codes are assigned to System B Address 204 Lighted keys indicate which user codes can bypass zones See also page 26 TLM options Address 206 key 2ND and key 1 The system verifies the...

Страница 19: ...time every day Program both the hour and minute addresses 245 246 for arming This will also be the auto test report time if enabled A late closing code may be programmed address 190 Related features...

Страница 20: ...ul for PBX systems which do not provide a dial tone You can program the dialing sequence required to get a line on a PBX system and this sequence will be added before the central station number If the...

Страница 21: ...stablished each subsequent new event will erase the oldest event in the buffer until the event buffer once again reaches 50 capacity Enable keypad panic signals Address 208 Key 1 on Panic 1 keys 1 and...

Страница 22: ...ll not cause an alarm on the associated burglar zone Panel Fire Zone Associated zone 728 3 4 ATZ 738 3 9 ATZ Arming Options Auto arm Address 210 Key 2 Key off When system auto arms on time or no movem...

Страница 23: ...l also be generated and communicated if an intellizone stays open for the total length of the designated intel lizone delay The intellizone delay which determines the period of time between 16 256 sec...

Страница 24: ...ral when there is no movement in the protected area for a designated time period Late to close If the system is not armed by a specified time addresses 245 246 the code programmed at address 190 SECTI...

Страница 25: ...255 minutes factory default 005 minutes Zone speed Address 251 Range 001 to 255 X 15mSec factory default 600 mSec Maximum time 3 8 seconds Power failure report delay Address 252 Range 001 to 255 minut...

Страница 26: ...any open zones will not be considered activated by the panel Open zones will not be protected and will not generate an alarm or prevent arming These away zones will become active and therefore protec...

Страница 27: ...occurred is stored in memory After disarming the system pressing once on the MEM key causes it to flash and brings up in the keypad display the alarm events that occurred during the last alarm period...

Страница 28: ...ot disarm the other system It is not possible to arm one system during the other system s exit delay Note When partitioning is not activated address 206 key 8 off Address 200 determines which access c...

Страница 29: ...p Each keypad is independently chime programmed and must be reprogrammed in the event of total power loss To enable a zone s chime feature press the desired zone key from 1 to 6 until a rapid intermit...

Страница 30: ...d within 60 seconds Key 7 Communicator report failure The control panel has unsuccessfully attempted to initiate communication with the central Report failure is stored in event list memory Key 8 Time...

Страница 31: ...xt reportable event installer code all communications 2 6 Installer test mode installer code only In installer test mode a confirmation beep intermittent indicates test is on a rejection beep long ind...

Страница 32: ...press CLEAR STREAMLINED PROGRAMMING Used to program sections 00 to 34 1 Press ENTER installer code 2 Key ENTER and 2ND will flash 3 Enter 2 digit section number 00 34 4 Enter 8 digit to program the se...

Страница 33: ...ND to erase a code Master code 00 10 10 Full access to all system functions User codes 01 16 01 can modify access codes All user code priorities can be programmed at addresses 200 202 204 with the ins...

Страница 34: ...maintain uninterrupted service GENERAL This equipment shall not be used on coin telephone lines Connection to party line service is subject to state tariffs RINGER EQUIVALENCE NUMBER REN The REN is u...

Страница 35: ...ERNANT LE RACCORDEMENT DE MAT RIEL L tiquette d Industrie Canada identifie le mat riel homologu Cette tiquette certifie que le mat riel est conforme certaines normes de protection d exploitation et de...

Страница 36: ...Installer Code 12 Installer Lock Installer Programming 23 11 23 Instant 21 Intellizone Definition 21 Intellizone Delay 12 Key Access Programming Keypads 29 6 11 Keypad panic alarm Keypad Zone Supervis...

Страница 37: ...INDEX 34 Zone Restore Transmission Zones With EOL Resistors 20...

Отзывы: