background image

USER MANUAL

 

UPS00100DC

 

© 

Panduit Corp. 2018

 

 

 

 

 

 

IA-CD-0009 Rev. 07 

                                                     Page 

15

 of 

46

 

3.5.

 

Service 

Have your UPS serviced by a qualified repair personnel using only identical replacement parts.  

Contact Panduit Customer Service and Technical Support at the following locations:

 

Customer Service 

800-777-3300 

Email:  [email protected] 

General Technical Support 

email:  [email protected] 

 

The information contained in this manual is based on experiences to date and is believed to be reliable.  It is 

intended as a Web Interface for use by personnel having technical skill at their own discretion and risk.  We do 

not guarantee favorable results or assume any liability in connection with its use.  Dimensions contained herein 

are for reference purposes only. For specific dimensional requirements consult the factory. This publication is not 

to be taken as a license to operate under or a recommendation to infringe any existing patents. 

 

4.

 

HARDWARE INSTALLATION 

4.1.

 

BACKGROUND 

The UPS is designed to be installed on a the EN 60715 NS35 DIN rail.  Use of this product in other applications 

is acceptable but other precautions may be required to allow for specific installations and are not covered in 

this manual. 

4.2.

 

PRODUCT INSPECTION/Registration 

Inspect the UPS for any visible signs of damage before installing. If damaged, please contact Panduit customer 

support at 1-800-777-3300 or 

[email protected]

.  

Please register your product to receive notification of firmware and product updates at: 

https://pages.panduit.com/Product-Registration-Request.html

 

4.3.

 

OVERVIEW 

The physical connections

3

 to the UPS are arranged on the top and bottom edge of the front panel on the unit. 

The top edge of the unit contains the functional interfaces which includes the input voltage source connections 

(INP 1+, INP 2-), the external sense resistor connections (SEN 3+, SEN 4-), the output voltage connections (OUT 

5+, OUT 6-), and the chassis ground (GRD 7).  The bottom edge of the unit contains the communication 

interfaces which includes the control output relay connections (CON 8, CON 9) and the Ethernet connections 

(‹…›10). The front panel also contains an ON/OFF power switch and three indicator LEDs.  The front panel is 

shown in Figure 4: UPS Front Panel Details. Refer to Figure 5 for the location of the reset button and serial 

number.  

                                                           

3

 Make sure to observe the polarity of the connections between the Power Supply and UPS, between the LSM and UPS, and 

between the Load and the UPS so they are properly connected. 

Содержание UPS00100DC

Страница 1: ...ument the UPS00100DC Uninterruptible Power Supply may also be referred to as UPS Email techsupport panduit com EU Website www panduit com emea 7 Technical Support Tel 1 888 506 5400 ext 83255 Panduit...

Страница 2: ...2 4 Environmental 9 2 5 Compliance 9 2 6 Installation 10 2 7 Performance 11 2 8 Indicators 11 2 9 Power Switch 11 2 10 Web User Interface 11 2 11 Network Interface 11 2 12 Shipping and Storage 11 2 1...

Страница 3: ...atus 22 5 4 2 Input Volts and Input Amps 23 5 4 3 Output Volts and Output Amps 23 5 4 4 Load Sense Amps 23 5 4 5 Uptime HHHHHH MM SS 23 5 4 6 Temperature deg C 23 5 4 7 State of Health 23 5 4 8 Events...

Страница 4: ...ING 44 7 1 LED STATUS INDICATORS 44 7 1 1 MOD LED Module Status Indicator 44 7 1 2 NET LED Network Status Indicator 45 7 1 3 CHG LED Charge Status Indicator 45 7 2 SNMP Traps 46 Table of Figures Figur...

Страница 5: ...n Pop up Window 36 Figure 26 Network Web Page 37 Figure 27 Device Name Change Pop up Window 37 Figure 28 Network Settings Change Web Page 38 Figure 29 Change Web Page 39 Figure 30 Charge Speed Change...

Страница 6: ...be accessed via a web browser running on a PC connected to the same network as the UPS The ON OFF switch may be used to turn the UPS off which removes voltage from the terminals so that the unit is s...

Страница 7: ...SE MODULE Please see the Load Sense Module UPS003LSM instruction manual for integrating the load sense module to your system Document number PA27224A01 is included with the LSM or on www panduit com T...

Страница 8: ...del Part Number UPS00100DC Panduit s 100 Watt Uninterruptible Power Supply 2 2 Input Power Voltage 24 0 to 28 0 VDC Power Minimum 24W with no load charging on slow charge setting per Section 5 8 2 Pow...

Страница 9: ...afety Part 1 General Requirements Low Voltage Directive IEC 60950 1 2005 A2 2013 EN60950 1 2006 A11 2009 A1 2010 A12 2010 A2 2013 Information Technology Equipment Safety Part 1 General Requirements Ro...

Страница 10: ...l cabinet enclosure or similar structure Restricted access can be provided by a door cover or similar physical means that requires the use of tools keys or other secure methods to gain access The leve...

Страница 11: ...low 11 to 15 minutes at nominal 22 5W Input Power 2 8 Indicators Module Status per The EtherNet IP Specification Volume 2 Chapter 9 Section 4 3 refer to Module Status Indicator Section 7 1 1 for detai...

Страница 12: ...l contractor or competent technician that meets the following qualifications Is thoroughly familiar with this product and the instructions for installation and operation Is trained accredited in indus...

Страница 13: ...d result from improper use of this UPS and responsibility for all necessary training to ensure safe operation of this UPS FOR INSTALLATION AND USE BY TRAINED PERSONNEL ONLY IF ANY DAMAGE TO THE PRODUC...

Страница 14: ...ere is an increased risk of electric shock if your body is earthed or grounded 3 3 Operation WARNING ONLY OPERATE THE UPS IN A CLEAN DRY INDOOR ENVIRONMENT DO NOT EXPOSE THE UPS TO RAIN OR WET CONDITI...

Страница 15: ...w for specific installations and are not covered in this manual 4 2 PRODUCT INSPECTION Registration Inspect the UPS for any visible signs of damage before installing If damaged please contact Panduit...

Страница 16: ...USER MANUAL UPS00100DC Panduit Corp 2018 IA CD 0009 Rev 07 Page 16 of 46 Figure 4 UPS Front Panel Details Figure 5 Reset Button and Serial Number...

Страница 17: ...intended to be hardwired at the customer site location It must be installed by a qualified electrician in compliance with all local and national regulations NOTE The UPS should be shipped with the po...

Страница 18: ...the National Electric Code ANSI NFPA 70 4 5 1 ON OFF POWER SWITCH This toggle switch enables operation of the UPS when it is set to the ON position When set to the OFF position the LEDs will be OFF a...

Страница 19: ...gend marked INP are to be connected to an external DC power supply The terminal marked is to be connected to the positive supply line from the power supply and the terminal marked is to be connected t...

Страница 20: ...offers added visibility through a separate communication channel PLC light stack etc The status of the relay follows the charge status indicator as shown in table below Table 2 Relay Contact Status 4...

Страница 21: ...s Charge Speed Slow Device Name Panduit UPS Network Settings DHCP Password UPS Serial Number Username Panduit UPS Language English These values may be changed through the WBI Connecting the UPS to the...

Страница 22: ...n does not resume after Restore Factory Defaults contact Panduit for technical support or service Table 3 Module Status Status Description Device Operational If the device is operating correctly the M...

Страница 23: ...d Output Amps Output Volts displays the DC Voltage present on the Output OUT 5 OUT 6 terminals When Input Power is present this may be a slightly lower value than Input Volts due to small losses withi...

Страница 24: ...he cell s that have an over voltage and the value of voltage that appeared on the cell s This is typically a hardware fault condition The UPS will continue to provide pass through power but the UPS ba...

Страница 25: ...strates some examples of the event log entries that the user may see 6 Figure 10 Even Log Web Page 5 4 8 2 REFRESH Clicking the REFRESH button provides an explicit command to retrieve the latest updat...

Страница 26: ...mber may be obtained from the label on the side of the UPS refer to Figure 5 Reset Button and Serial Number It is strongly recommended to change the Username and Password from the factory default valu...

Страница 27: ...l Number and MAC ID values 5 6 1 MODEL The Model displays the Model Number of this UPS device The UPS00100DC is the model number of the 100 Watt UPS that has been received with this User Manual This M...

Страница 28: ...5 6 3 SERIAL NUMBER The Serial Number displays the Serial Number of this UPS device that is printed onto a label on the side of the unit The Serial Number is also used as the factory default value fo...

Страница 29: ...ing on the CHANGE button allows the user to change the default Username A pop up window shown below queries the user to enter a new Username Click in the text box and an X will appear at the end of th...

Страница 30: ...he user for the next action to be taken Click the in the Save button and select Save As Select the location on the PC that the file should be saved in and note the location for later use Exit out of t...

Страница 31: ...s After a Restore to Factory Defaults the user should perform a RESET Figure 17 Restore Pop up Window 5 6 10 LANGUAGE The current Language for the WBI is displayed Clicking on the down arrow displays...

Страница 32: ...he SNMP agent is disabled To enable the SNMP agent click the EDIT button next to the version of SNMP you want to support Clicking on the SNMP EDIT button will pop up a window to enable the SNMP agent...

Страница 33: ...w to change the IP Port referred to as the SNMP Agent port from the default value of 162 Click the SAVE button to update the port value Click the CANCEL button to cancel the updates After performing t...

Страница 34: ...is located and who is responsible for managing it Clicking on the System EDIT button will pop up a window to change the System Contact and System Location from the default values of SNMP sysContact an...

Страница 35: ...moved click the REMOVE button next the user being removed See the image below for an example creating a public and private community string for the UPS Click the SAVE button to update the SNMP communi...

Страница 36: ...w is used to setup the IP Address of the SNMP manager that will be receiving the trap notifications the port default SNMP Trap port is 162 then whether the SNMP trap should be sent as SNMP v1 v2c or v...

Страница 37: ...evice Name A pop up window shown below queries the user to enter a new Device Name Click in the text box and an X will appear at the end of the text box Clicking the x will clear the current Device Na...

Страница 38: ...nd Static The pop up window shown below queries the user to select the new Network Setting A check mark in the SELECT box indicates the current network setting Click the DHCP or STATIC SELECT button t...

Страница 39: ...eed setting Slow or Fast The Fast charge speed results in the fastest charge Table 5 UPS Charge Speed Power and Time Charge Speed Maximum Charge Power Approximate Charging Time Fast 31 8 Watts 10 5 mi...

Страница 40: ...the energy used for cell balancing NOTE Charge time is only updated during charge mode 5 8 5 CHARGE LEVEL Charge Level represents the percentage of energy stored in the capacitors This value should b...

Страница 41: ...e operating temperature of the UPS Figure 6 DIN Rail Installation below shows the Estimated UPS Life with respect to the operating ambient temperature of the UPS Table 6 Estimated UPS Life Based on Te...

Страница 42: ...en 6 5 STATUS VIA PC Status information and control of the UPS may be accessed via a web browser on a PC that is connected to the same network that the UPS is connected The UPS will be assigned an IP...

Страница 43: ...ectory on your hard drive 3 Use the EDS Hardware Installation tool to install the EDS files This tool is installed with RSLinx software under the RSLinxTools directory It is also installed with RSLogi...

Страница 44: ...circuited output Reduce the load or remove the short from output pins Turn the UPS Power Switch OFF then ON to clear the Fault Inconsistent Configuration Re configure the UPS via Web UI or perform Res...

Страница 45: ...een only when all timed out Exclusive Owner connections arc reestablished Devices that support a single Exclusive Owner Connection shall transition to steady green when subsequent Exclusive Owner Conn...

Страница 46: ...ger available Cell Overtemperature Fault One or more of the cells has an unexpected high voltage the UPS has transitioned to end of life The UPS will continue to pass input power to output but backup...

Отзывы: