Alerting/Communication wiring is along the bottom edge of the UPS.
o
Control Output: Isolated, SPST-NO (Form A) contact, rated 30 VDC at 1A maximum that may be
connected to an alarm. Contact will be closed when the output of the UPS is providing power.
o
Communications: RJ45 jack for Ethernet (10BaseT) communications.
2.7.
Performance
•
Hold Time: Typically, 1 minute ± 15% with a 100W load connected to the output terminals. The Hold Time
will vary depending on the State of Health of the UPS. The Hold Time is also affected by the load: a lighter
load will result in a longer Hold Time.
•
Voltage Drop: 500 mV maximum from Input to Output when Input power is present.
•
Output Transition Transient: 5 ms max, 18 to 23 VDC with a 100W load present (transient when
transitioning from pass through to UPS backup power).
•
Ripple Voltage: 50 mVp-p max. over 20 Hz to 20 MHz.
•
Charge Times:
o
Fast:
9 to 12 minutes at nominal 31.8W Input Power
o
Slow:
11 to 15 minutes at nominal 22.5W Input Power
2.8.
Indicators
•
Module Status: per The EtherNet/IP Specification (Volume 2, Chapter 9 Section 4.3) – refer to Module
Status Indicator Section 7.1.1 for details.
•
Network Status: per The EtherNet/IP Specification (Volume 2, Chapter 9 Section 4.4) – refer to Network
Status Indicator Section 7.1.2 for details.
•
Charge Status – refer to Charge Status Indicator Section 7.1.3 for details.
2.9.
Power Switch
•
A toggle switch to enable and disable UPS operations – refer to ON/OFF POWER SWITCH Section 4.5.1 for
details.
2.10.
Web User Interface
•
IP Address: Dynamic by default: the UPS requires DHCP server on the same subnet to establish
communications. The UPS could be reconfigured to a Static IP Address. Refer to the Network Section 5.7 on
how to change this setting.
•
Content (Available pages in the WBI):
o
Module
o
Network
o
Charge
o
Settings
2.11.
Network Interface
•
Protocol: Ethernet/IP, operating as a slave, Generic Profile
•
Certification: ODVA
2.12.
Shipping and Storage
NOTE: The UPS must be stored or shipped with the power switch turned ON
•
Refer to ON/OFF POWER SWITCH Section 4.5.1 for removing the UPS from service and preparing it for
shipping or storage.