CABINET SENSOR HARDWARE INSTALLATION
MANUAL
42
Installing the Subfloor Sensor (Mesh, Solid or Glass Doors, or Open Frames)
1. Locate an access hole in the
cabinet bottom and insert the
subfloor sensor and cable.
2. Insert the subfloor sensor and cable
through the access hole in the
raised floor.
3. Using a tile puller, remove the floor
tile adjacent to the area where
subfloor sensor is located.
4. Secure the sensor to the subfloor
stanchion with a plenum-rated
cable tie.
5. Replace floor tile with tile puller.
Proceed to
Validating and Commissioning the ThermaNode Installation
.
Dual Inlet Cabinet Installation
The dual inlet cabinet configuration has two cabinets with louvered vents (chimneys)
positioned back-to-back with exhaust sides facing each other. Cabinet intake doors face
outward and opposite of each other.
N
OTE
:
In this section, cable assembly wiring is red, cable ties are yellow, and sensors
are light blue.
Dual Inlet ThermaNode Cable Assembly
The Dual Inlet Cabinet Sensor cable assembly installs on the outside of the cabinet
doors and routes across the cabinet tops with a single exhaust sensor positioned
between the exhaust chimneys.