CABINET SENSOR HARDWARE INSTALLATION
MANUAL
22
Installing ThermaNode EZs
with Cable ties
If bracket installation methods do not work
for the installation, use cable ties to install
the node.
1. Insert a cable tie through the mounting
hole at each corner of the node.
2. Insert cable tie ends through mounting
holes/surface positioning “S” vents close
to the door centerline.
3. Secure the cable tie on the inside of the
cabinet and clip cable tie excess close
to the locking mechanism.
4. Repeat the previous steps to mount the
next node according to the MapSense
layout.
Dual Inlet Cabinet Configurations
The dual inlet cabinet has two cabinets with louvered exhaust vents (chimneys)
positioned back-to-back and facing each other. Cabinet intake doors face outward and
opposite of each other.
The diagram shows ThermaNode EZs on a dual inlet cabinet: two
sensors on each intake side and one exhaust sensor at the top
(chimney).
For mesh, solid door, or open frames, install the ThermaNode EZ
according to the instructions provided in the previous sections:
•
Solid Door and Open Frame Installation