CABINET SENSOR HARDWARE INSTALLATION
MANUAL
31
Cable ties
Use cable ties to fasten components to mesh doors by inserting cable ties through
each of the module mounting holes and around the mesh.
•
Gather loose wire by making a small looping bundle and secure with cable ties
•
Attach cable ties to the inside of door such that the locking mechanism is always on the inside
•
Use cable ties in adjacent holes of mesh door to keep the loop appearing on the outside as small
as possible
•
Pull wire(s) taut to prevent slippage but not so tight as to cause pinched wiring or crushed
sensors
•
Use diagonal cutters to clip cable tie ends close to its locking mechanism
NOTE:
A 36" extension cable is available for additional length between intake and
exhaust sides.
Sensor Placement
Sensors locations are at “U” levels and continue down
the centerline of the cabinet at the top, middle, and
bottom levels. Sensor placement is important to ensure
accurate cabinet temperature readings.
NOTE:
If sensor placement location changes from the original floor plan (such as
moving to a different cabinet), be sure to update the floor plan in MapSense.
For double doors, install sensors
on one door, approximately one
inch from the edge of the mesh,
farthest from the door hinge.
Ensure disconnects are on the
door side of the hinge to allow door
removal.
An optional subfloor sensor,
attached to the bottom disconnect
of the exhaust sensor wiring, can
be routed through a hole in a floor