CABINET SENSOR HARDWARE INSTALLATION
MANUAL
33
Installing ThermaNode Cabinet Sensor Kits
This section provides steps for installing the ThermaNode cable assembly in cabinets
with mesh or solid doors, open frames, and dual inlets. See
information regarding rear exhaust and top exhaust cabinet configurations.
N
OTE
:
The ThermaNode Sensor should be installed at least 15 ft. away from the Wi-Fi
access point.
After installing the ThermaNode Cabinet Sensor Kits, see
Validating and
Commissioning the ThermaNode Installation
. Finally, see
complete the installation process.
Preparing to Install ThermaNode Sensor Kits
The SynapSense Field Engineer is responsible for confirming installation readiness and
completing these preparation steps:
1. Assure the following steps are complete:
•
Required software is installed and configured.
•
Gateways are installed and powered on.
•
All products and tools necessary for installation are on site.
2. Verify the receipt of quantities and contents listed on packing/shipping list found in
Box 1.
•
Place kits in front of each cabinet numbers on the kit bag (or as numbered on
the printed MapSense layout).
•
Verify install team has all necessary tools and additional materials to complete
installation and site is ready for installation.
3. For ThermaNodes with MAC IDs that have not yet been recorded or scanned, follow
these steps:
•
Record the ThermaNode MAC IDs manually, or with a barcode scanner and
upload into MapSense.
•
Access the site layout from the MapSense application. Refer to the MapSense
User Guide.
•
Add and configure the appropriate ThermaNode objects and associated IDs in
the data center floor plan.
4. Export the
MapSense
project *.dlz file from MapSense for viewing in Web Console.
5. For cable assembly installations with subfloor sensors, determine where the subfloor
sensor routing will be located (rack and into the subfloor area).