CONNECT THE CABLE TO THE OUTDOOR UNIT

4

(FOR DETAIL REFER TO WIRING DIAGRAM AT UNIT)
1.  Attach the discharge grille (left side) 

3

 for safety before connecting the cable.

4 claw hooks

Screw 

5

 in 4 places

2.  Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed fl exible cable (see below table), type 

designation 60245 IEC 57 or heavier cable. Sheath diameter of connecting cable shall be within specifi cation (see below table) to fi t cable gland.

Flexible cable specifi cation

Cable diameter

4 × min 2.5mm

2

 

ø12.0-14.0

3.  Route the cable as follows

*

1

 Locally procured cabtyre cables with the specifi ed diameter.

*

2

 Must be fastened with the specifi ed torque Viewpoint of gas intrusion prevention.

Remove the front plate (Fig. 4-1)

Remove the terminal cover and cable gland cap (Fig. 4-2)

3  

Insert the cabtyre cable *1 (Fig. 4-3, 4-4)
(Pulled in from the rear panel and inserted from the bottom of the electric controller BOX)

4

 Connect to terminal block (Fig. 4-5)

5

 Fasten the cable gland *2 (Fig. 4-4)

6

 Set the terminal cover *2 (Fig. 4-2)

7

 Set the front plate (Fig. 4-1)

From 
Indoor unit

Fig. 4 - 3

Fig. 4 - 1

Fig. 4 - 2

Tightening torque : 
147.1 ~ 245.2 cN•m
(15 ~ 25 k

g

f•cm)

Terminal cover

Cable gland

Cable gland 
cap disposal

The cabinet top plate does not need to be removed.

The nut does not need to be removed.
If accidentally the nut is removed, fasten to 
the following torque.
Tightening torque :  220 ~ 300 cN•m

(22.43 ~ 30.59 k

g

f•cm)

Fasten the cable gland
Tightening torque : 
180 ~ 250 cN•m
(18.35 ~ 25.49 k

g

f•cm)

Pass the cable through the cable gland.

Fig. 4 - 4

Fasten with 
the cable tie.

Pass the cable 
through the groove.

Cabtyre cable

If it is diffi cult to pass 
the cable through, the 
cover can be removed.

Содержание WH-WDG05LE5

Страница 1: ... be installed The caution items stated here must be followed because these important contents are related to safety The meaning of each indication used is as below Incorrect installation due to ignoring or negligence of the instruction will cause harm or damage and the seriousness is classified by the following indications Please leave the installation manual with the unit after installation WARNI...

Страница 2: ...eakage during operation Extinguish all fire sources if present It may lead to the risk of fire or explosion when the refrigerant contacts with fire Only use the supplied or specified installation parts else it may cause unit vibrate loose water leakage electrical shock or fire If there is any doubt about the installation procedure or operation always contact the authorized dealer for advice and in...

Страница 3: ...ations Must ensure mechanical connections be accessible for maintenance purposes In cases that require mechanical ventilation ventilation openings shall be kept clear of obstruction When disposal of the product do follow to the precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel Any qualified person ...

Страница 4: ...charging recovering or purging the system That there is continuity of earth bonding At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance If a fault exists that could compromise safety then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with If the faul...

Страница 5: ...re is ventilation available 9 Charging procedures In addition to conventional charging procedures the following requirements shall be followed Ensure that contamination of different refrigerants does not occur when using charging equipment Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position accordin...

Страница 6: ...ings and in good condition Before using the recovery machine check that it is in satisfactory working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the re...

Страница 7: ...d this outdoor unit There must be no building openings windows doors light shafts cellar entrances escape hatches flat roof windows or ventilation openings in the protective zone There must be no ignition sources such as heat above 360 C sparks open flame plug sockets light switches lamps electrical switches or other permanent ignitions sources in the protective zone The protective zone must not e...

Страница 8: ...to tighten the hose at drain hose connector to prevent it from leaking Drain elbow 1 Rubber cap 2 After selecting the best location start installation according to Installation Diagram 1 When installing at roof please consider strong wind and earthquake Please fasten the installation stand firmly with bolt or nails 2 When installing to a concrete or solid surface use M10 or a W 3 8 bolts and nuts ...

Страница 9: ...ate Fig 4 1 2 Remove the terminal cover and cable gland cap Fig 4 2 3 Insert the cabtyre cable 1 Fig 4 3 4 4 Pulled in from the rear panel and inserted from the bottom of the electric controller BOX 4 Connect to terminal block Fig 4 5 5 Fasten the cable gland 2 Fig 4 4 6 Set the terminal cover 2 Fig 4 2 7 Set the front plate Fig 4 1 From Indoor unit Fig 4 3 Fig 4 1 Fig 4 2 Tightening torque 147 1 ...

Страница 10: ... 2 Remove the 3 screws Fasten the 3 screws Insert 4 claws WARNING This equipment must be properly earthed Terminals on the indoor unit 1 2 3 Colour of wires Terminals on the outdoor unit 1 2 3 Terminal screw Tightening torque cN m kgf cm M4 157 196 16 20 M5 196 245 20 25 1 2 3 Earth Wire must be longer than other wires for safety reason Screw Cable gland 5 mm or more gap between wires Indoor outdo...

Отзывы: