12. Recovery

 

• When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are 

removed safely.

 

• When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed.

 

• Ensure that the correct number of cylinders for holding the total system charge are available.

 

• All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant).

 

• Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order.

 

• Recovery cylinders are evacuated and, if possible, cooled before recovery occurs.

 

• The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be 

suitable for the recovery of fl ammable refrigerants.

 

• Make sure the recovery equipment is not a potential ignition source and is suitable for the refrigerant you are using.

 

• In addition, a set of calibrated weighing scales shall be available and in good working order.

 

• Hoses shall be complete with leak-free disconnect couplings and in good condition.

 

• Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated 

electrical components are sealed to prevent ignition in the event of a refrigerant release.
Consult manufacturer if in doubt.

 

• The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged.

 

• Do not mix refrigerants in recovery units and especially not in cylinders.

 

• If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that 

fl ammable refrigerant does not remain within the lubricant.

 

• The evacuation process shall be carried out prior to returning the compressor to the suppliers.

 

• Only electric heating to the compressor body shall be employed to accelerate this process.

 

• When oil is drained from a system, it shall be carried out safely.

Attached accessories

No.

Accessories part

Qty.

1

Drain elbow

1

2

Rubber cap

3

3

Discharge grille (left side)

1

4

Discharge grille (right side)

1

5

Screw

4

Optional accessories

No.

Accessories part

Qty.

6

Base Pan Heater
CZ-NE4P

1

 

• It is strongly recommended to install a Base Pan Heater (optional) 

if the outdoor unit is install in cold climate area. Refer the Base Pan 
Heater (optional) installation instruction for details of installation.

Содержание WH-WDG05LE5

Страница 1: ... be installed The caution items stated here must be followed because these important contents are related to safety The meaning of each indication used is as below Incorrect installation due to ignoring or negligence of the instruction will cause harm or damage and the seriousness is classified by the following indications Please leave the installation manual with the unit after installation WARNI...

Страница 2: ...eakage during operation Extinguish all fire sources if present It may lead to the risk of fire or explosion when the refrigerant contacts with fire Only use the supplied or specified installation parts else it may cause unit vibrate loose water leakage electrical shock or fire If there is any doubt about the installation procedure or operation always contact the authorized dealer for advice and in...

Страница 3: ...ations Must ensure mechanical connections be accessible for maintenance purposes In cases that require mechanical ventilation ventilation openings shall be kept clear of obstruction When disposal of the product do follow to the precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel Any qualified person ...

Страница 4: ...charging recovering or purging the system That there is continuity of earth bonding At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance If a fault exists that could compromise safety then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with If the faul...

Страница 5: ...re is ventilation available 9 Charging procedures In addition to conventional charging procedures the following requirements shall be followed Ensure that contamination of different refrigerants does not occur when using charging equipment Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position accordin...

Страница 6: ...ings and in good condition Before using the recovery machine check that it is in satisfactory working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the re...

Страница 7: ...d this outdoor unit There must be no building openings windows doors light shafts cellar entrances escape hatches flat roof windows or ventilation openings in the protective zone There must be no ignition sources such as heat above 360 C sparks open flame plug sockets light switches lamps electrical switches or other permanent ignitions sources in the protective zone The protective zone must not e...

Страница 8: ...to tighten the hose at drain hose connector to prevent it from leaking Drain elbow 1 Rubber cap 2 After selecting the best location start installation according to Installation Diagram 1 When installing at roof please consider strong wind and earthquake Please fasten the installation stand firmly with bolt or nails 2 When installing to a concrete or solid surface use M10 or a W 3 8 bolts and nuts ...

Страница 9: ...ate Fig 4 1 2 Remove the terminal cover and cable gland cap Fig 4 2 3 Insert the cabtyre cable 1 Fig 4 3 4 4 Pulled in from the rear panel and inserted from the bottom of the electric controller BOX 4 Connect to terminal block Fig 4 5 5 Fasten the cable gland 2 Fig 4 4 6 Set the terminal cover 2 Fig 4 2 7 Set the front plate Fig 4 1 From Indoor unit Fig 4 3 Fig 4 1 Fig 4 2 Tightening torque 147 1 ...

Страница 10: ... 2 Remove the 3 screws Fasten the 3 screws Insert 4 claws WARNING This equipment must be properly earthed Terminals on the indoor unit 1 2 3 Colour of wires Terminals on the outdoor unit 1 2 3 Terminal screw Tightening torque cN m kgf cm M4 157 196 16 20 M5 196 245 20 25 1 2 3 Earth Wire must be longer than other wires for safety reason Screw Cable gland 5 mm or more gap between wires Indoor outdo...

Отзывы: