background image

5

7.  The following leak detection methods are deemed acceptable for all refrigerant systems.

 

• No leaks shall be detected when using detection equipment with a sensitivity of 5 grams per year of refrigerant or better under a pressure of at 

least 0,25 times the maximum allowable pressure (>0.98MPa, max 3.90MPa). For example, a universal sniffer.

 

• Electronic leak detectors may be used to detect fl ammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration.

(Detection equipment shall be calibrated in a refrigerant-free area.)

 

• Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used.

 

• Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the 

appropriate percentage of gas (25 % maximum) is confi rmed.

 

• Leak detection fl uids are also suitable for use with most refrigerants, for example, bubble method and fl uorescent method agents. The use of 

detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.

 

• If a leak is suspected, all ignition sources shall be removed/extinguished.

 

• If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system.

The precautions in #8 must be followed to remove the refrigerant.

8.  Removal and evacuation

 

• When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used.

However, it is important that best practice is followed since fl ammability is a consideration.
The following procedure shall be adhered to:

• remove refrigerant -> • purge the circuit with inert gas -> • evacuate -> • purge with inert gas -> • open the circuit by cutting. 
Brazing must not be used.

 

• The refrigerant charge shall be recovered into the correct recovery cylinders.

 

• The system shall be purged with OFN to render the appliances safe. (remark: OFN = oxygen free nitrogen, type of inert gas)

 

• This process may need to be repeated several times.

 

• Compressed air or oxygen shall not be used for this task.

 

• Purging shall be achieved by breaking the vacuum in the system with OFN and continuing to fi ll until the working pressure is achieved, then 

venting to atmosphere, and fi nally pulling down to a vacuum.

 

• This process shall be repeated until no refrigerant is within the system. (Until the concentration of purge gas is 0.25 LFL or less by the leak 

detector). 

0.25LFL = 0.525Vol%

 

• When the fi nal OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.

 

• This operation is absolutely vital if brazing operations on the pipe work are to take place.

 

• Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and there is ventilation available.

9. Charging procedures

 

• In addition to conventional charging procedures, the following requirements shall be followed.

-  Ensure that contamination of different refrigerants does not occur when using charging equipment.

-  Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.

-  Cylinders shall be kept in an appropriate position according to the instructions.

-  Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.

-  Label the system when charging is complete (if not already).

-  Extreme care shall be taken not to over fi ll the refrigerating system.

 

• Prior to recharging the system it shall be pressure tested with OFN (refer to #8).

 

• The system shall be leak tested on completion of charging but prior to commissioning.

 

• A follow up leak test shall be carried out prior to leaving the site.

 

• Electrostatic charge may accumulate and create a hazardous condition when charging and discharging the refrigerant.

To avoid fi re or explosion, dissipate static electricity during transfer by grounding and bonding containers and equipment before charging/discharging.

10. Decommissioning

 

• Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its details.

 

• It is recommended good practice that all refrigerants are recovered safely.

 

• Re-use of recovered refrigerant is prohibited.

 

• It is essential that electrical power is available before the task is commenced.

a)  Become familiar with the equipment and its operation.
b)  Isolate system electrically.
c)  Before attempting the procedure ensure that:

d)  Make sure that cylinder is situated on the scales before recovery 

takes place.

e)  Start the recovery machine and operate in accordance with 

instructions.

f)  Do not over fi ll cylinders. (No more than 80 % volume liquid 

charge).

g)  Do not exceed the maximum working pressure of the cylinder, 

even temporarily.

h)  When the cylinders have been fi lled correctly and the process 

completed, make sure that the cylinders and the equipment 
are removed from site promptly and all isolation valves on the 
equipment are closed off.

 

• mechanical handling equipment is available, if required, 

for handling refrigerant cylinders;

 

• all personal protective equipment and leak detectors are 

available and being used correctly;

 

• the recovery process is supervised at all times by a 

competent person;

 

• recovery equipment and cylinders conform to the 

appropriate standards.

 

• Electrostatic charge may accumulate and create a hazardous condition when charging or discharging the refrigerant.

To avoid fi re or explosion, dissipate static electricity during transfer by grounding and bonding containers and equipment before charging/discharging.

11. Labelling

 

• Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant.

 

• The label shall be dated and signed.

 

• Ensure that there are labels on the equipment stating the equipment contains fl ammable refrigerant.

Содержание WH-WDG05LE5

Страница 1: ... be installed The caution items stated here must be followed because these important contents are related to safety The meaning of each indication used is as below Incorrect installation due to ignoring or negligence of the instruction will cause harm or damage and the seriousness is classified by the following indications Please leave the installation manual with the unit after installation WARNI...

Страница 2: ...eakage during operation Extinguish all fire sources if present It may lead to the risk of fire or explosion when the refrigerant contacts with fire Only use the supplied or specified installation parts else it may cause unit vibrate loose water leakage electrical shock or fire If there is any doubt about the installation procedure or operation always contact the authorized dealer for advice and in...

Страница 3: ...ations Must ensure mechanical connections be accessible for maintenance purposes In cases that require mechanical ventilation ventilation openings shall be kept clear of obstruction When disposal of the product do follow to the precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel Any qualified person ...

Страница 4: ...charging recovering or purging the system That there is continuity of earth bonding At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance If a fault exists that could compromise safety then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with If the faul...

Страница 5: ...re is ventilation available 9 Charging procedures In addition to conventional charging procedures the following requirements shall be followed Ensure that contamination of different refrigerants does not occur when using charging equipment Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position accordin...

Страница 6: ...ings and in good condition Before using the recovery machine check that it is in satisfactory working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the re...

Страница 7: ...d this outdoor unit There must be no building openings windows doors light shafts cellar entrances escape hatches flat roof windows or ventilation openings in the protective zone There must be no ignition sources such as heat above 360 C sparks open flame plug sockets light switches lamps electrical switches or other permanent ignitions sources in the protective zone The protective zone must not e...

Страница 8: ...to tighten the hose at drain hose connector to prevent it from leaking Drain elbow 1 Rubber cap 2 After selecting the best location start installation according to Installation Diagram 1 When installing at roof please consider strong wind and earthquake Please fasten the installation stand firmly with bolt or nails 2 When installing to a concrete or solid surface use M10 or a W 3 8 bolts and nuts ...

Страница 9: ...ate Fig 4 1 2 Remove the terminal cover and cable gland cap Fig 4 2 3 Insert the cabtyre cable 1 Fig 4 3 4 4 Pulled in from the rear panel and inserted from the bottom of the electric controller BOX 4 Connect to terminal block Fig 4 5 5 Fasten the cable gland 2 Fig 4 4 6 Set the terminal cover 2 Fig 4 2 7 Set the front plate Fig 4 1 From Indoor unit Fig 4 3 Fig 4 1 Fig 4 2 Tightening torque 147 1 ...

Страница 10: ... 2 Remove the 3 screws Fasten the 3 screws Insert 4 claws WARNING This equipment must be properly earthed Terminals on the indoor unit 1 2 3 Colour of wires Terminals on the outdoor unit 1 2 3 Terminal screw Tightening torque cN m kgf cm M4 157 196 16 20 M5 196 245 20 25 1 2 3 Earth Wire must be longer than other wires for safety reason Screw Cable gland 5 mm or more gap between wires Indoor outdo...

Отзывы: