9
ENGLISH
Cold water supply
Pressure reducing valve
(fi eld supply)
Safety valve
Inlet pipe
Expansion vessel
(fi eld supply)
Tee Joint
(fi eld supply)
Drain valve
(fi eld supply)
Tee Joint
(fi eld supply)
>300mm
<600mm
<600mm
Tundish
(fi eld supply)
1. Connect the tundish and route the discharge pipe as shown
above. Tundish should be visible and positioned away from frost
environment and electrical components.
2. The tundish should be fi tted vertically and as close to the safety
device as possible and within 600mm of the device.
3. The tundish should be visible to users and positioned away from
electrical devices.
4. The discharge pipe from the tundish should be terminate in a safe
place where there is no risk to person nearby to the discharge, be
of metal construction and:
A) Be at least one pipe size larger than the nominal outlet size of
the safety device unless its total equivalent hydraulic resistance
exceeds that of a straight pipe 9m long. Bends must be taken
into account in calculating the fl ow resistance.
B) Have a vertical section of pipe at least 300mm long, below the
tundish before any elbows or bends in the pipework.
C) Be installed with a continuous fall.
D) Have discharges visible at both the tundish and fi nal point of
discharge.
CONNECT THE CABLE TO THE
TANK UNIT
4
WARNING
This section is for authorized and licensed electrician only. Work
behind the Control Board Cover
3
secured by screws must only
be carried out under supervision of qualifi ed contractor, installation
engineer or service person.
Fixing of Power Supply Cable and Connecting Cable
1. Connecting cable between Tank Unit and Outdoor Unit shall be
approved polychloroprene sheathed fl exible cord, type designation
60245 IEC 57 or heavier cord. See below table for cable size requirement.
Model
Connecting
Cable Size
Tank Unit
Outdoor Unit
WH-ADC0309J3E5UK
WH-UD03JE5, WH-UD05JE5 4 x min 1.5 mm
2
WH-UD07JE5, WH-UD09JE5 4 x min 2.5 mm
2
•
Ensure the colour of wires of Outdoor Unit and the terminal no.
are the same to the Tank Unit respectively.
•
Earth wire shall be longer than the other wires as shown in the
fi gure for the electrical safety in case of the slipping out of the
cord from the Holder (Clamper).
2. An isolating device must be connected to the power supply cable.
•
Isolating device (disconnecting means) should have minimum
3.0 mm contact gap.
•
Connect the approved polychloroprene sheathed power supply
1 cord and power supply 2 cord and type designation 60245
IEC 57 or heavier cord to the terminal board, and to the other
end of the cord to isolating device (Disconnecting means).
See below table for cable size requirement.
Model
Power
Supply
Cord
Cable Size
Isolating
Devices
Recommended
RCD
Tank Unit
Outdoor Unit
WH-ADC0309J3E5UK
WH-UD03JE5,
WH-UD05JE5
1
3 x min 1.5 mm
2
15/16A 30mA, 2P, type A
2
3 x min 1.5 mm
2
15/16A 30mA, 2P, type AC
WH-UD07JE5,
WH-UD09JE5
1
3 x min 2.5 mm
2
25A
30mA, 2P, type A
2
3 x min 1.5 mm
2
15/16A 30mA, 2P, type AC
3. To avoid the cable and cord being damaged by sharp edges, the cable
and cord must be passed through a bushing (located at the bottom
of Control Board) before terminal board. The bushing must be used
and must not be removed.
Terminals on the Outdoor Unit
1
2
3
Colour of wires (Connecting cables)
Terminals on the Tank unit
L
N
L
1
N
1
1
2
3
(Power Supply Cord)
Terminals on the isolating devices
from power supply (Disconnecting
means)
L
N
L
1
N
1
Tank Unit/
Outdoor Unit
connection
Power Supply 1 Power Supply 2
Power Supply Cable
Holder (Clamper)
Terminal Board
RCCB/ELCB
*1
Connecting Cable
Terminal screw
Tightening torque cN•m {kgf•cm}
M4
157~196 {16~20}
M5
196~245 {20~25}
*1 - Earth wire must be longer than other cables for safety reasons
WIRE STRIPPING AND CONNECTING REQUIREMENT
5mm or more
(gap between wires)
Indoor/outdoor
connecting
terminal board
Wire stripping
No loose strand
when insert
10 ± 1mm
ACCEPT
PROHIBITED
Conductor
over insert
Conductor not
fully insert
Conductor
fully insert
PROHIBITED
CONNECTING REQUIREMENT
For Tank Unit with WH-UD03JE5, WH-UD05JE5, WH-UD07JE5,
WH-UD09JE5
•
The equipment’s Power Supply 1 complies with IEC/EN 61000-3-2.
•
The equipment’s Power Supply 1 complies with IEC/EN 61000-3-3
and can be connected to current supply network.
•
The equipment’s Power Supply 2 complies with IEC/EN 61000-3-2.
•
The equipment’s Power Supply 2 complies with IEC/EN 61000-
3-11 and shall be connected to suitable supply network, with the
following maximum permissible system impedance Z
max
= 0.352
ohm (
) at the interface. Please liaise with supply authority to
ensure that the Power Supply 2 is connected only to a supply of
that impedance or less.