33
ENGLISH
29. Outdoor temp. for (Cool to Heat)
Initial setting: 10°C
10°
C
Heat
Cool
Outdoor temp. dropping
Set outdoor temp that switches from Cooling to Heating by Auto setting.
Setting range is 5°C ~ 25°C
Timing of judgement is every 1 hour
Tank
30. Floor operation time (max)
Initial setting: 8h
Heat
Tank
30min ~ 10h
Set max operating hours of heating.
When max operation time is shortened, it can boil the tank more frequently.
It is a function for H Tank operation.
31. Tank heat up time (max)
Initial setting: 60min
Heat
Tank
5min ~ 4h
Set max boiling hours of tank.
When max boiling hours are shortened, it immediately returns to Heating
operation, but it may not fully boil the tank.
32. Tank re-heat temp.
Initial setting: -8°C
-12°C ~ -2°C
Set temp to perform reboil of tank water.
(When boiled by heat pump only, (51°C – Tank re-heat temp) shall become
max temp.)
Setting range is -12°C ~ -2°C
33. Sterilization
Initial setting: 65°C 10min
②
① ③
Set timer to perform sterilization.
1
Set operating day & time. (Weekly timer format)
2
Sterilization temp (55~75°C
If use back-up heater, it is 65°C)
3
Operation time (Time to run sterilization when it reached setting temp
5min ~ 60min)
User shall set whether to use or not to use sterilization mode.
Содержание WH-UD03JE5
Страница 36: ...Printed in the Czech Republic ACXF60 37631 AB ...