Booster heater control
- Booster heater turn On and Off follow normal operation.
- Booster heater turn ON condition:
1 During startup time (initialization), Booster heater turn ON after DELAY TIMER.
2 When tank temperature lower than HEATER ON TEMP
3 20 minutes from previous heater off.
- Booster heater turn OFF condition:
1 When tank temperature higher than tank set temperature for continuous 15 secs.
Solar 3 way valve
- Solar pump operates follow solar operation specification.
2 way valve closes
Others
- Indoor backup heater cannot be ON during tank mode only.
Содержание WH-MDF12C6E5
Страница 12: ...12 4 Location of Controls and Components 4 1 Mono bloc Unit ...
Страница 13: ...13 4 1 1 Main Components ...
Страница 15: ...15 ...
Страница 16: ...16 ...
Страница 17: ...17 4 1 3 Weekly Timer Setting ...
Страница 18: ...18 4 1 4 Setting Up The Special Functions ...
Страница 19: ...19 5 Dimensions 5 1 Mono bloc Unit ...
Страница 20: ...20 6 Refrigeration and Water Cycle Diagram ...
Страница 21: ...21 ...
Страница 22: ...22 7 Block Diagram ...
Страница 23: ...23 8 Wiring Connection Diagram ...
Страница 24: ...24 ...
Страница 25: ...25 9 Electronic Circuit Diagram ...
Страница 26: ...26 ...
Страница 27: ...27 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Страница 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Страница 29: ...29 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 30: ...30 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Страница 31: ...31 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Страница 32: ...32 Main Components ...
Страница 42: ...42 ...
Страница 48: ...48 ...
Страница 49: ...49 ...
Страница 59: ...59 ...
Страница 107: ...107 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Страница 115: ...115 ...
Страница 119: ...119 19 2 WH MDF12C6E5 WH MDF14C6E5 WH MDF16C6E5 WH MDF12C6E5 1 WH MDF14C6E5 1 WH MDF16C6E5 1 Water System ...