Troubleshooting by Indication on the Remote Controller
Troubleshooting
185
3.37
“
L8
”
Outdoor Unit:
Inverter Current Abnormal
Remote
Controller
Display
L8
Applicable
Models
U-4..6ML5DPQ, U-4..6ML5XPQ
Method of
Malfunction
Detection
Malfunction is detected by current flowing in the power transistor.
Malfunction
Decision
Conditions
When overload in the compressor is detected.
Supposed
Causes
Compressor overload
Compressor coil disconnected
Defect of outdoor unit PC board (A2P)
Troubleshooting
(V3184)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Output current check
Inverter
output
voltage check
Inverter output voltage
is not balanced
(Normal if within
±
5V). Must
be measured when
frequency
is stable.
Compressor overload
Inspection of the compressor and
refrigerant system is required.
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration
and operating status of the
compressor.
NO
Replace the inverter PC board
assy (A2P).
YES
NO
Reset and restart.
NO
The
secondary
current of the inverter is
higher than 13.1A,
260 sec. for
each phase.
Replace the compressor.
NO
YES
Compressor
inspection The
compressor's coil is
disconnected.
YES
YES
Disconnect the the connection
between the compressor and
inverter. Make the power
transistor check mode setting
ON by service mode.
After turning
on again, "
L8
" blinks
again.
Panasonic
Содержание U-4..6ML5XPQ
Страница 1: ...Service Manual U 4 6ML5XPQ DPQ Urban Multi Mini UM Heat Pump ...
Страница 2: ......
Страница 12: ...Introduction x Urban Multi ML5 Mini UM Heat Pump ...
Страница 17: ...Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 10 Panasonic ...
Страница 37: ...Specifications Specifications 25 Panasonic ...
Страница 38: ...Specifications 26 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Страница 39: ...Specifications Specifications 27 Panasonic ...
Страница 40: ...Specifications 28 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Страница 134: ...Field Setting 122 Test Operation Urban Multi ML5 Mini UM Heat Pump ...
Страница 235: ...Piping Diagrams Appendix 223 U 4 5 6ML5DPQ 3D052712 Panasonic ...
Страница 238: ...Piping Diagrams 226 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 239: ...Wiring Diagrams Appendix 227 2 Wiring Diagrams 2 1 Outdoor Unit U 4 5 6ML5XPQ 3D059640 Panasonic ...
Страница 240: ...Wiring Diagrams 228 Appendix U 4 5 6ML5DPQ 3D05811B Urban Multi ML5 Mini UM Heat Pump ...
Страница 241: ...Wiring Diagrams Appendix 229 2 2 Field Wiring U 4 5 6ML5XPQ 3D057919 Panasonic ...
Страница 242: ...Wiring Diagrams 230 Appendix U 4 5 6ML5DPQ 3D052597 Urban Multi ML5 Mini UM Heat Pump ...
Страница 243: ...Wiring Diagrams Appendix 231 2 3 Indoor Unit S 20 25 32 63LM3HPQ Panasonic ...
Страница 244: ...Wiring Diagrams 232 Appendix S 40 50 80 125LM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 245: ...Wiring Diagrams Appendix 233 S 20 25 32 40 50 63 80 100 125UM4JPQ Panasonic ...
Страница 246: ...Wiring Diagrams 234 Appendix S 20 25 32 40 50YM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 247: ...Wiring Diagrams Appendix 235 S 25 32 40 63DM3HPS 3D039564C Panasonic ...
Страница 248: ...Wiring Diagrams 236 Appendix S 20 25NM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 249: ...Wiring Diagrams Appendix 237 S 20 25 32 40 50 63FM3HPQ Panasonic ...
Страница 250: ...Wiring Diagrams 238 Appendix S80 100 125FM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 252: ...Wiring Diagrams 240 Appendix S 32 63 100TM3JPR 3D039801D Urban Multi ML5 Mini UM Heat Pump ...
Страница 255: ...Wiring Diagrams Appendix 243 Panasonic ...
Страница 256: ...Wiring Diagrams 244 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 257: ...Wiring Diagrams Appendix 245 Panasonic ...
Страница 259: ...Option List Appendix 247 Panasonic ...
Страница 262: ...Example of Connection 250 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 283: ......