Troubleshooting by Indication on the Remote Controller
Troubleshooting
179
3.31
“
J9
”
Outdoor Unit:
Malfunction of Thermistor (R4T)
Remote
Controller
Display
J9
Applicable
Models
U-4..6ML5DPQ, U-4..6ML5XPQ
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by subcooling heat exchanger
gas pipe thermistor.
Malfunction
Decision
Conditions
When the subcooling heat exchanger gas pipe thermistor is short circuited or open.
Supposed
Causes
Faulty subcooling heat exchanger gas pipe thermistor (R4T)
Faulty outdoor unit PC board
Troubleshooting
∗
Refer to “Thermistor Resistance / Temperature Characteristics” table on P251.
(V3075)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
resistance
measured after
removing the thermistor
(R4T) from outdoor unit PC
board normal?
(3.5 k
Ω
to
360 k
Ω
)
Replace outdoor unit PC board
(A1P).
Connect connector and operate
unit again.
NO
NO
Replace thermistor (R4T).
YES
YES
Is
the connector
for subcooling heat
exchanger gas pipe
thermistor connected to
X12A of outdoor unit
PC board
(A1P)?
Panasonic
Содержание U-4..6ML5XPQ
Страница 1: ...Service Manual U 4 6ML5XPQ DPQ Urban Multi Mini UM Heat Pump ...
Страница 2: ......
Страница 12: ...Introduction x Urban Multi ML5 Mini UM Heat Pump ...
Страница 17: ...Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 10 Panasonic ...
Страница 37: ...Specifications Specifications 25 Panasonic ...
Страница 38: ...Specifications 26 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Страница 39: ...Specifications Specifications 27 Panasonic ...
Страница 40: ...Specifications 28 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Страница 134: ...Field Setting 122 Test Operation Urban Multi ML5 Mini UM Heat Pump ...
Страница 235: ...Piping Diagrams Appendix 223 U 4 5 6ML5DPQ 3D052712 Panasonic ...
Страница 238: ...Piping Diagrams 226 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 239: ...Wiring Diagrams Appendix 227 2 Wiring Diagrams 2 1 Outdoor Unit U 4 5 6ML5XPQ 3D059640 Panasonic ...
Страница 240: ...Wiring Diagrams 228 Appendix U 4 5 6ML5DPQ 3D05811B Urban Multi ML5 Mini UM Heat Pump ...
Страница 241: ...Wiring Diagrams Appendix 229 2 2 Field Wiring U 4 5 6ML5XPQ 3D057919 Panasonic ...
Страница 242: ...Wiring Diagrams 230 Appendix U 4 5 6ML5DPQ 3D052597 Urban Multi ML5 Mini UM Heat Pump ...
Страница 243: ...Wiring Diagrams Appendix 231 2 3 Indoor Unit S 20 25 32 63LM3HPQ Panasonic ...
Страница 244: ...Wiring Diagrams 232 Appendix S 40 50 80 125LM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 245: ...Wiring Diagrams Appendix 233 S 20 25 32 40 50 63 80 100 125UM4JPQ Panasonic ...
Страница 246: ...Wiring Diagrams 234 Appendix S 20 25 32 40 50YM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 247: ...Wiring Diagrams Appendix 235 S 25 32 40 63DM3HPS 3D039564C Panasonic ...
Страница 248: ...Wiring Diagrams 236 Appendix S 20 25NM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 249: ...Wiring Diagrams Appendix 237 S 20 25 32 40 50 63FM3HPQ Panasonic ...
Страница 250: ...Wiring Diagrams 238 Appendix S80 100 125FM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 252: ...Wiring Diagrams 240 Appendix S 32 63 100TM3JPR 3D039801D Urban Multi ML5 Mini UM Heat Pump ...
Страница 255: ...Wiring Diagrams Appendix 243 Panasonic ...
Страница 256: ...Wiring Diagrams 244 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 257: ...Wiring Diagrams Appendix 245 Panasonic ...
Страница 259: ...Option List Appendix 247 Panasonic ...
Страница 262: ...Example of Connection 250 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 283: ......