Symptom-based Troubleshooting
Troubleshooting
125
1. Symptom-based Troubleshooting
Symptom
Supposed Cause
Countermeasure
1
The system does not start operation at all.
Blowout of fuse(s)
Turn Off the power supply and
then replace the fuse(s).
Cutout of breaker(s)
• If the knob of any breaker is in
its OFF position, turn ON the
power supply.
• If the knob of any circuit
breaker is in its tripped position,
do not turn ON the power
supply.
Power failure
After the power failure is reset,
restart the system.
Open phase in power supply
cable
Check power supply. After that,
properly connect the power
supply cable, and then turn ON
the power supply.
2
The system starts operation but makes an
immediate stop.
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
3
The system does not cool or heat air well.
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
Enclosed outdoor unit(s)
Remove the enclosure.
Improper set temperature
Set the temperature to a proper
degree.
Airflow rate set to "LOW"
Set it to a proper airflow rate.
Improper direction of air diffusion
Set it to a proper direction.
Open window(s) or door(s)
Shut it tightly.
[In cooling] Direct sunlight received
Hang curtains or shades on
windows.
[In cooling] Too many persons staying in a
room
[In cooling] Too many heat sources (e.g. OA
equipment) located in a room
4
The system does
not operate.
The system stops and
immediately restarts operation.
If the OPERATION lamp on the
remote controller turns ON, the
system will be normal. These
symptoms indicate that the
system is controlled so as not to
put unreasonable loads on the
system.
Normal operation. The system will
automatically start operation after
a lapse of five minutes.
Pressing the TEMP ADJUST
button immediately resets the
system.
The remote controller displays
"UNDER CENTRALIZED
CONTROL", which blinks for a
period of several seconds
when the OPERATION button
is depressed.
The system is controlled with
centralized controller. Blinking
display indicates that the system
cannot be operated using the
remote controller.
Operate the system using the
COOL/HEAT centralized remote
controller.
The system stops immediately
after turning ON the power
supply.
The system is in preparation
mode of micro computer
operation.
Wait for a period of approximately
one minute.
5
The system
makes
intermittent
stops.
The remote controller displays
malfunction codes "U4" and
"U5", and the system stops but
restarts after a lapse of several
minutes.
The system stops due to an
interruption in communication
between units caused by
electrical noises coming from
equipment other than air
conditioners.
Remove causes of electrical
noises.
If these causes are removed, the
system will automatically restart
operation.
ON
OFF
Knob
Tripped
Circuit breaker
Panasonic
Содержание U-4..6ML5XPQ
Страница 1: ...Service Manual U 4 6ML5XPQ DPQ Urban Multi Mini UM Heat Pump ...
Страница 2: ......
Страница 12: ...Introduction x Urban Multi ML5 Mini UM Heat Pump ...
Страница 17: ...Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 10 Panasonic ...
Страница 37: ...Specifications Specifications 25 Panasonic ...
Страница 38: ...Specifications 26 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Страница 39: ...Specifications Specifications 27 Panasonic ...
Страница 40: ...Specifications 28 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Страница 134: ...Field Setting 122 Test Operation Urban Multi ML5 Mini UM Heat Pump ...
Страница 235: ...Piping Diagrams Appendix 223 U 4 5 6ML5DPQ 3D052712 Panasonic ...
Страница 238: ...Piping Diagrams 226 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 239: ...Wiring Diagrams Appendix 227 2 Wiring Diagrams 2 1 Outdoor Unit U 4 5 6ML5XPQ 3D059640 Panasonic ...
Страница 240: ...Wiring Diagrams 228 Appendix U 4 5 6ML5DPQ 3D05811B Urban Multi ML5 Mini UM Heat Pump ...
Страница 241: ...Wiring Diagrams Appendix 229 2 2 Field Wiring U 4 5 6ML5XPQ 3D057919 Panasonic ...
Страница 242: ...Wiring Diagrams 230 Appendix U 4 5 6ML5DPQ 3D052597 Urban Multi ML5 Mini UM Heat Pump ...
Страница 243: ...Wiring Diagrams Appendix 231 2 3 Indoor Unit S 20 25 32 63LM3HPQ Panasonic ...
Страница 244: ...Wiring Diagrams 232 Appendix S 40 50 80 125LM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 245: ...Wiring Diagrams Appendix 233 S 20 25 32 40 50 63 80 100 125UM4JPQ Panasonic ...
Страница 246: ...Wiring Diagrams 234 Appendix S 20 25 32 40 50YM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 247: ...Wiring Diagrams Appendix 235 S 25 32 40 63DM3HPS 3D039564C Panasonic ...
Страница 248: ...Wiring Diagrams 236 Appendix S 20 25NM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 249: ...Wiring Diagrams Appendix 237 S 20 25 32 40 50 63FM3HPQ Panasonic ...
Страница 250: ...Wiring Diagrams 238 Appendix S80 100 125FM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 252: ...Wiring Diagrams 240 Appendix S 32 63 100TM3JPR 3D039801D Urban Multi ML5 Mini UM Heat Pump ...
Страница 255: ...Wiring Diagrams Appendix 243 Panasonic ...
Страница 256: ...Wiring Diagrams 244 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 257: ...Wiring Diagrams Appendix 245 Panasonic ...
Страница 259: ...Option List Appendix 247 Panasonic ...
Страница 262: ...Example of Connection 250 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 283: ......