Test Operation
Test Operation
83
Malfunction code
In case of an alarm code displayed on remote controller:
Malfunction
code
Nonconformity during installation
Remedial action
E3
The shutoff valve of an outdoor unit is left
closed.
Open the gas-side shutoff valve and the liquid-side shutoff valve.
Refrigerant overcharge.
Recalculate the required amount of refrigerant from the piping
length and correct the refrigerant charge level by recovering any
excessive refrigerant with a refrigerant recovery machine.
E4
The shutoff valve of an outdoor unit is left
closed.
Open the gas-side shutoff valve and the liquid-side shutoff valve.
Insufficient refrigerant.
Check if the additional refrigerant charge has been finished
correctly.
Recalculate the required amount of refrigerant from the piping
length and add an adequate amount of refrigerant.
F3
Refrigerant overcharge.
Recalculate the required amount of refrigerant from the piping
length and correct the refrigerant charge level by recovering any
excessive refrigerant with a refrigerant recovery machine.
The shutoff valve of an outdoor unit is left
closed.
Open the gas-side shutoff valve and the liquid-side shutoff valve.
Insufficient refrigerant.
Check if the additional refrigerant charge has been finished
correctly.
Recalculate the required amount of refrigerant from the piping
length and add an adequate amount of refrigerant.
F6
Refrigerant overcharge
Recalculate the required amount of refrigerant from the piping
length and correct the refrigerant charge level by recovering any
excessive refrigerant with a refrigerant recovery machine.
U1
Power supply cables are connected in the
reverse phase instead of the normal phase.
Connect the power supply cables in normal phase. Change any
two of the three power supply cables (L1, L2, L3) to correct phase.
U2
Insufficient supply voltage
Check to see if the supply voltage is supplied properly.
U3
If a check operation has not been
performed.
Perform a check operation.
U4
No power is supplied to an outdoor unit.
Turn the power on for the outdoor unit.
UA
If no dedicated indoor unit is being used.
Check the indoor unit. If it is not a dedicated unit, replace the
indoor unit.
UF
The shutoff valve of an outdoor unit is left
closed.
Open the gas-side shutoff valve and the liquid-side shutoff valve.
If the right indoor unit piping and wiring are
not properly connected to the outdoor unit.
Make sure that the right indoor unit piping and wiring are properly
connected to the outdoor unit.
UH
If the interunit wiring has not be connected
or it has shorted.
Make sure the interunit wiring is correctly attached to terminals
(X2M) F1/F2 (TO IN/D UNIT) on the outdoor unit circuit board.
Panasonic
Содержание U-4..6ML5XPQ
Страница 1: ...Service Manual U 4 6ML5XPQ DPQ Urban Multi Mini UM Heat Pump ...
Страница 2: ......
Страница 12: ...Introduction x Urban Multi ML5 Mini UM Heat Pump ...
Страница 17: ...Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 10 Panasonic ...
Страница 37: ...Specifications Specifications 25 Panasonic ...
Страница 38: ...Specifications 26 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Страница 39: ...Specifications Specifications 27 Panasonic ...
Страница 40: ...Specifications 28 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Страница 134: ...Field Setting 122 Test Operation Urban Multi ML5 Mini UM Heat Pump ...
Страница 235: ...Piping Diagrams Appendix 223 U 4 5 6ML5DPQ 3D052712 Panasonic ...
Страница 238: ...Piping Diagrams 226 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 239: ...Wiring Diagrams Appendix 227 2 Wiring Diagrams 2 1 Outdoor Unit U 4 5 6ML5XPQ 3D059640 Panasonic ...
Страница 240: ...Wiring Diagrams 228 Appendix U 4 5 6ML5DPQ 3D05811B Urban Multi ML5 Mini UM Heat Pump ...
Страница 241: ...Wiring Diagrams Appendix 229 2 2 Field Wiring U 4 5 6ML5XPQ 3D057919 Panasonic ...
Страница 242: ...Wiring Diagrams 230 Appendix U 4 5 6ML5DPQ 3D052597 Urban Multi ML5 Mini UM Heat Pump ...
Страница 243: ...Wiring Diagrams Appendix 231 2 3 Indoor Unit S 20 25 32 63LM3HPQ Panasonic ...
Страница 244: ...Wiring Diagrams 232 Appendix S 40 50 80 125LM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 245: ...Wiring Diagrams Appendix 233 S 20 25 32 40 50 63 80 100 125UM4JPQ Panasonic ...
Страница 246: ...Wiring Diagrams 234 Appendix S 20 25 32 40 50YM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 247: ...Wiring Diagrams Appendix 235 S 25 32 40 63DM3HPS 3D039564C Panasonic ...
Страница 248: ...Wiring Diagrams 236 Appendix S 20 25NM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 249: ...Wiring Diagrams Appendix 237 S 20 25 32 40 50 63FM3HPQ Panasonic ...
Страница 250: ...Wiring Diagrams 238 Appendix S80 100 125FM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 252: ...Wiring Diagrams 240 Appendix S 32 63 100TM3JPR 3D039801D Urban Multi ML5 Mini UM Heat Pump ...
Страница 255: ...Wiring Diagrams Appendix 243 Panasonic ...
Страница 256: ...Wiring Diagrams 244 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 257: ...Wiring Diagrams Appendix 245 Panasonic ...
Страница 259: ...Option List Appendix 247 Panasonic ...
Страница 262: ...Example of Connection 250 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 283: ......