Field Setting
116
Test Operation
Setting of Demand Operation
By connecting the external contact input to the demand input of the outdoor unit external control
adaptor (optional), the power consumption of unit operation can be saved suppressing the
compressor operating condition.
When the normal demand operation is carried out. (Use of the external control adaptor
for outdoor unit is not required.)
1. While in "Setting mode 2", make setting of the set item No. 32 (Setting of constant demand)
to "ON".
2. While in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then
set the setting condition to targeted mode.
Image of operation
Set item
Condition
Content
Demand
Mode 1
The compressor operates at approx. 60% or less of rating.
Mode 2
The compressor operates at approx. 70% or less of rating.
Mode 3
The compressor operates at approx. 80% or less of rating.
(V3082)
The power consumption set with "Demand 1 level setting".
When the
"Normal demand
setting" is set to ON
("OFF" has been set
at factory.) , the
power consumption
can be set with the
"Demand 1 level
setting". ("70 % of
rated power
consumption" has
been set at factory.)
Power consumption
Rated power consumption
80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption
Urban Multi ML5 · Mini UM · Heat Pump
Содержание U-4..6ML5XPQ
Страница 1: ...Service Manual U 4 6ML5XPQ DPQ Urban Multi Mini UM Heat Pump ...
Страница 2: ......
Страница 12: ...Introduction x Urban Multi ML5 Mini UM Heat Pump ...
Страница 17: ...Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 10 Panasonic ...
Страница 37: ...Specifications Specifications 25 Panasonic ...
Страница 38: ...Specifications 26 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Страница 39: ...Specifications Specifications 27 Panasonic ...
Страница 40: ...Specifications 28 Specifications Urban Multi ML5 Mini UM Heat Pump ...
Страница 134: ...Field Setting 122 Test Operation Urban Multi ML5 Mini UM Heat Pump ...
Страница 235: ...Piping Diagrams Appendix 223 U 4 5 6ML5DPQ 3D052712 Panasonic ...
Страница 238: ...Piping Diagrams 226 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 239: ...Wiring Diagrams Appendix 227 2 Wiring Diagrams 2 1 Outdoor Unit U 4 5 6ML5XPQ 3D059640 Panasonic ...
Страница 240: ...Wiring Diagrams 228 Appendix U 4 5 6ML5DPQ 3D05811B Urban Multi ML5 Mini UM Heat Pump ...
Страница 241: ...Wiring Diagrams Appendix 229 2 2 Field Wiring U 4 5 6ML5XPQ 3D057919 Panasonic ...
Страница 242: ...Wiring Diagrams 230 Appendix U 4 5 6ML5DPQ 3D052597 Urban Multi ML5 Mini UM Heat Pump ...
Страница 243: ...Wiring Diagrams Appendix 231 2 3 Indoor Unit S 20 25 32 63LM3HPQ Panasonic ...
Страница 244: ...Wiring Diagrams 232 Appendix S 40 50 80 125LM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 245: ...Wiring Diagrams Appendix 233 S 20 25 32 40 50 63 80 100 125UM4JPQ Panasonic ...
Страница 246: ...Wiring Diagrams 234 Appendix S 20 25 32 40 50YM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 247: ...Wiring Diagrams Appendix 235 S 25 32 40 63DM3HPS 3D039564C Panasonic ...
Страница 248: ...Wiring Diagrams 236 Appendix S 20 25NM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 249: ...Wiring Diagrams Appendix 237 S 20 25 32 40 50 63FM3HPQ Panasonic ...
Страница 250: ...Wiring Diagrams 238 Appendix S80 100 125FM3HPQ Urban Multi ML5 Mini UM Heat Pump ...
Страница 252: ...Wiring Diagrams 240 Appendix S 32 63 100TM3JPR 3D039801D Urban Multi ML5 Mini UM Heat Pump ...
Страница 255: ...Wiring Diagrams Appendix 243 Panasonic ...
Страница 256: ...Wiring Diagrams 244 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 257: ...Wiring Diagrams Appendix 245 Panasonic ...
Страница 259: ...Option List Appendix 247 Panasonic ...
Страница 262: ...Example of Connection 250 Appendix Urban Multi ML5 Mini UM Heat Pump ...
Страница 283: ......