3.6 Muting Function (Only for ST4-C12EX)
61
ST4-A□
S (m/s)
1
1
2
3
Sensing object
Physical
barrier
Physical
barrier
Muting sensor B’
Muting sensor A’
Muting sensor B
Muting sensor A
Safety zone
Dangerous zone
1. The distance between muting
sensors A to A' and between B to
B' must be shorter than the whole
length of the object to be sensed.
2. The distance between muting
sensors A and B has to be covered
by the object to be sensed in less
than 3 seconds. (S = speed)
Distance between A and B:
S × 3 (s)
3. The distance between muting
sensors A' and B' has to be
covered by the object to be sensed
in less than 3 seconds.
Distance between A' and B':
S × 3 (s)
Muting
sensor A
ON
OFF
Muting
sensor B
ON
OFF
Muting
sensor A’
ON
OFF
Muting
sensor B’
ON
OFF
Muting lamp
output
ON
OFF
Auxiliary output 1
(AUX 1)
ON
OFF
0 to 3 sec.
25ms or less
50ms to 1 sec. (Note 1)
Sensing object
(Within the
protective area)
ON
OFF
Present
Absent
Control output
(OSSD 1 / 2)
Valid muting time (Note 2)
Time diagram for the muting function
NOTE
1. When the diagnosis function for the muting lamp (see page 74) is active: If
the muting lamp does not light up after 1s, the muting function is
deactivated.
When diagnosis function for the muting lamp (see page 74) is not active: The
muting function is activated with a delay of 50ms after the input conditions of
the muting sensor A (A') and B (B') are satisfied.
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12
www.sentronic.com
Produkte, Support und Service
SENTRONIC
AG