7-3
When only ERROR3 lights
There is no terminal resistance, or noise is added on the wiring.
Connect the wiring correctly, and eliminate the noise.
When only ERROR4 lights
There is a broken or disconnected wire in the S-LINK, or there is an error in an S-LINK device. If this
happens, set the RUN/CHK. selector switch to the “CHK.” position, and press the system SET button.
This displays the address of the S-LINK I/O device where the error occurred in the address display
window (if errors have occurred at multiple addresses, the display changes seq uentially each time the
system SET button is pressed).
This error is retained. Turn off the S-LINK main and local power supplies, and repair the broken or
disconnected wire, or eliminate the problem with the input/output unit. Then turn on the S-LINK main and
local power supplies.