2-4
Fuse
A 8A-tubular fuse of 5 mm x 20 mm is used (provided as an accessory).
For the replacement, use a UL/CSA-approved time-lag type fuse.
Transmission indicator (SEND)
It blinks during communicating I/O data between each S-LINK device on the S-LINK system.
It is synchronized with the communication frames, so that the blinking cycle gets slow as the number of
total I/O points is large.
ERROR indicators
These light if an error occurs in the S-LINK system.
ERR1 (Error 1): Short circuit between D-G line.
ERR3 (Error 3): Abnormal voltage level between D-G line.
ERR4 (Error 4): Broken wire or I/O S-LINK device error
Note:
•
If ERR1 (Error 1) lights (there is little possibility that ERR1 (Error 1) occurs by itself), the protective
function which guards against a short-circuit between D and G has been activated.
To cancel the protective function, turn off the power supply to the S-LINK, and then repair the cause of
the short-circuit. (The short-circuit protective function is maintained as long as the power supply to the
S-LINK is on.)
•
If the power supply to the S-LINK is turned off, ERR1 (Error 1) and ERR3 (Error 3) light.
•
ERR4 (Error 4) is maintained after repairing. To cancel this error, either turn the power supply to the
FP
Σ
off and then on again, or press the SET switch to reset it when the RUN/CHK. selector switch is
set to the RUN position, or turn the power supply to the S-LINK off and then on again.
•
If the signal line is broken or the power supply to the booster is cut off, errors occur on more than one
I/O S-LINK devices.
ADDRESS display (2-digit hexadecimal display)
This displays the transmission status, the number of connected S-LINK devices, and the addresses of
the various S-LINK devices. (Refer to “
RUN/CHK. selector switch” and “
SET switch”.
During normal transmission:
The “
” shaped character rotates in the clockwise direction.
If an error occurs:
This displays an abnormal address number. In case faults occur on several
I/O S-LINK devices, the decimal pints light up, and the smallest error address
of the S-LINK device which the error occurs is displayed.
Содержание S-Link FP2
Страница 1: ......
Страница 6: ......
Страница 7: ...1 1 Chapter 1 Selecting the Right Equipment...
Страница 11: ...2 1 Chapter 2 Specifications...
Страница 18: ...2 8...
Страница 19: ...3 1 Chapter 3 I O Assignments...
Страница 24: ...3 6...
Страница 25: ...4 1 Chapter 4 Construction and Wiring...
Страница 28: ...4 4...
Страница 29: ...5 1 Chapter 5 Starting and Ending Operations...
Страница 37: ...6 1 Chapter 6 Shared Memory...
Страница 45: ...7 1 Chapter 7 What To Do If An Error Occurs...
Страница 50: ...7 6...
Страница 51: ...8 1 Chapter 8 Dimensions...
Страница 52: ...8 2 8 1 Dimensions FPG SL AFPG780...
Страница 54: ......