7-4
7.2 Judging by Error Codes
7.2.1 E34 (I/O Status Error) Occurred
When E34 (I/O status error) occurred in the control unit, the MODE switch of the S-LINK unit has been
set to either No. 1, No. 7 or No. D.
Use the numbers other than the above numbers.
7.2.2 E42 (I/O Verify Error) Occurred
When E42 (I/O verify error) occurred in the control unit, the MODE switch of the S-LINK unit has been
changed after the power supply was turned on.
The MODE switch should be changed when the power supply of the FP
Σ
is off.
7.3 Judging by Address Display
7.3.1 Function of Address Display
When the system is functioning normally, the “
” display rotates.
If an error occurs at an address in the S-LINK (an S-LINK device), that address is displayed as a
numeric value.
Example