56
Remote control display
Alarm contents
E14
Two or more indoor units are set as main, in the group controlled indoor units.
E15
Fewer indoor units are found in Auto Addressing than the setting on outdoor PCB.
E16
More indoor units are found in Auto Addressing than the setting on outdoor PCB.
E18
No response from sub indoor to the main indoor unit in group control wiring.
E20
No indoor unit responded in Auto Addressing.
E31
Error in communication inside outdoor unit control box.
F01
Indoor unit heat exchanger liquid temperature sensor has failure. (E1)
F02
Indoor unit heat exchanger temperature sensor has failure. (E2)
F03
Indoor unit heat exchanger gas temperature sensor has failure. (E3)
F04
Compressor 1 discharge temperature sensor has failure. (DISCH1)
F06
Outdoor unit heat exchanger 1 gas temperature sensor has failure. (EXG1)
F07
Outdoor unit heat exchanger 1 liquid temperature sensor has failure. (EXL1)
F08
Outdoor temperature sensor has failure. (TO)
F10
Indoor suction air (room) temperature sensor has failure. (TA)
F11
Indoor discharge air temperature sensor has failure. (BL)
F12
Compressor inlet temperature sensor has failure. (SCT)
F14
Subcooling heat exchanger temperature sensor has failure. (SCG)
F16
High pressure sensor has failure. (HPS)
F17
Low pressure sensor has failure. (LPS)
F29
EEPROM on indoor unit PCB has failure.
F31
EEPROM on outdoor unit PCB has failure.
H01
Compressor 1 primary current is overcurrent.
H02
PFC is overcurrent or VDC is overvoltage.
H03
Compressor 1 current sensor is disconnected or shorted.
H05
Compressor 1 discharge temperature sensor is disconnected, shorted or misplaced. (DISCH1)
H06
Low pressure sensor value is too low.
H31
Compressor 1 HIC has failure. HIC is overcurrent or overheat. VDC is undervoltage or overvoltage.
L01
Indoor unit address setting has error. (No main indoor unit in group control.)
L02
Indoor unit model does not match with the outdoor unit model. (Multi-split/mini-split)
L03
Two or more indoor units are set as main in group control.
L04
Duplicate system address setting on outdoor units.
L05
Two or more indoor units are set as priority indoor unit (priority indoor unit).
L06
Two or more indoor units are set as priority indoor unit (non-priority indoor unit).
L07
Group control wiring is detected for indoor unit set as individual control.
L08
Indoor unit address is not set.
L09
Capacity setting of indoor unit is not correct.
L10
Capacity setting of outdoor unit is not correct.
L13
Indoor unit model does not match with outdoor unit.
L17
Model mismatch between outdoor units.
L18
4-way valve has failure.
P01
Thermal protector for Indoor unit fan motor is activated.
P03
Compressor 1 discharge temperature is too high.
P04
High pressure swich is activated.
P05
AC power supply has abnormal.
P09
Connection to the panel of indoor unit is not good.
P10
Float switch of drain pan safety is activated.
P11
Drain pump failure or locked rotor.
P12
Indoor unit fan inverter protection control is activated.
P14
O
2
sensor has activated.
P16
Compressor 1 secondary current is overcurrent.
P20
Too high load in refrigerant circuit.
P22
Outdoor unit fan 1 motor has failure.
P29
Compressor start failure. Compressor is missing phase or reverse phase.
P31
Other indoor unit in group control has an alarm.