Panasonic KT7 Скачать руководство пользователя страница 11

11

8. Operation flowchart

Outline of operation procedure

Operation before running

[Step 1 Initial setting]

: Set Input type, Alarm type, control action, etc.

in Auxiliary function setting mode 2.

[Step 2 Adjusting item]

: Set PID values and Alarm value in the Sub setting

mode.

[Step 3 Lock setting]

: Set the Set value Lock in Auxiliary function setting

mode 1 (If Step 3 is not necessary, skip this step.)

[Step 4 Run setting]

: Set the SV(desired value) in the Main setting mode.

Set value lock

PV

SV

Selection

• Make a selection with

,

keys

.

• If Lock 1 or Lock2 is selected,

AT or Auto-reset does not work.

• Be sure to designate Lock 3 when

using Serial communication.

[Auxiliary function setting mode 1]

AT

PV

SV

Selection

• If AT is cancelled during the process,

PID values revert to previous value.

SV (Desired value)

PV

SV

SV

Integral time

PV

SV

Set value

• Set the value with

,

keys.

• PD action when set to 0, and auto-

reset can be performed.

OUT proportional

band

PV

SV

Set value

• Set the value with

,

keys.

• ON/OFF action when set to 0 or 0.0

Derivative time

PV

SV

Set value

• Set the value with

,

keys.

• Setting the value to 0 disables the

function.

OUT proportional

cycle

PV

SV

Set value

• Set the value with

,

keys.

• Not available for DC current output or

when OUT is ON/OFF action

Manual reset

PV

SV

Set value

• Set the value with

,

keys.

• Not available when OUT2 is ON/OFF

action

ARW

PV

SV

Set value

• Set the value with

,

keys.

• Available for PID action

Alarm value

PV

SV

Set value

• Set the value with

,

keys.

• Not available if

is selected

during Alarm action selection

Heater burnout alarm value

PV

.

SV

Set value

• Set the value with

,

keys.

Setting the value to 0.0 disables the function.

Reverts to the PV/SV display.

Reverts to PV/SV display.

[Main setting mode]

[Sub setting mode]

PV/SV display

Output MV indication

Press the

key.

Explanation of

key

: This means that

if

is pressed, the set

value is saved, and the
controller proceeds to the
next setting item.

Alarm setting procedure
(Numbers (1) to (6) are indicated on the flowchart.)

(1) [Alarm type]: Select an alarm type

(If an alarm type except for

is selected, items (2) to (6)

are indicated and they can be set if necessary.

(2) [Alarm action Energized/Deenergized]: Select Alarm contact output

ON (Energized:

) or OFF (Deenergized:

).

(3) [Alarm HOLD function]: Select the alarm output Holding or Not Holding.
(4) [Alarm hysteresis]: Set the Alarm hysteresis.
(5) [Alarm action delayed timer]: Set Alarm action delayed time.

(If input enters alarm action range and setting time has passed,
the alarm is activated.)

(6) [Alarm value]: Set action point of Alarm output.

[Note] If an alarm type is changed, the alarm set value

becomes 0 (0.0). Therefore it is necessary to reset it.

Setting items with dotted lines are optional
and they appear only when the options are
added.

Loop break alarm

action time

PV

SV

Set value

• Set the value with

,

keys.

• Setting the value to 0 disables the

function.

Loop break alarm

action span

PV

SV

Set value

• Set the value with

,

keys.

• Setting the value to 0 disables the

function.

Sensor correction

PV

SV

Set value

• Set the value with

,

keys.

Communication protocol

PV

SV

Selection

• Make a selection with

,

keys.

• Not available for

indication

Instrument number

PV

SV

Set value

• Set the value with

,

keys.

Communication speed

PV

SV

Selection

• Make a selection with

,

keys.

Stop bit

PV

SV

Selection

• Make a selection with

,

keys.

• Not available if

is selected

during Communication protocol
selection

Reverts to the PV/SV display.

Parity

PV

SV

Selection

•Make a selection with

,

keys.

• Not available if

is selected

during Communication protocol
selection

(6)

Press the

key

for approx. 3sec.

Press the

key.

Press the

key while holding down the

key.

Press

for approx. 3sec while holding down

.

Содержание KT7

Страница 1: ...ions it may malfunction or cause fire Be sure to follow the warnings cautions and notice If not it could cause serious injury or accidents The contents of this instruction manual are subject to change without notice This instrument is designed to be installed in a control panel If not measures must be taken to ensure that the operator cannot touch power terminals or other high voltage sections Be ...

Страница 2: ... Auxiliary function setting mode 2 in combination with the Mode key Fig 2 1 Notice When setting the specifications and functions of this controller connect terminals 1 and 2 for power source first then set them referring to 5 Setup and 8 Operation flowchart before performing 3 Mounting to the control panel and 4 Wiring 3 Mounting to the control panel 3 1 Site selection This instrument is intended ...

Страница 3: ...d horizontally in a position susceptible to vibration or shock the fastening plates must be used as well Recommended fastening plate Fastening plate ATA4806 1 Hook A of KT7 series on the upper side of the DIN rail Fig 3 4 1 2 Making B part of the KT7 series as a support fit the lower part of the KT7 series to the DIN rail KT7 series will be completely fixed to DIN rail with a Click sound Fig 3 4 1...

Страница 4: ...mocouple RTD etc away from power source and load wires to avoid external interference To prevent the unit from harmful effects of the unexpected level noise it is recommended that a surge absorber be installed between the electromagnetic switch coils This unit does not have built in power switch circuit breaker or fuse Therefore it is necessary to install them in the circuit externally near the co...

Страница 5: ...limit to SV high limit or scaling low limit value to scaling high limit value For DC voltage and current inputs the placement of the decimal point follows the selection 5 2 Sub setting mode Character PV display Name Description Setting range Default value SV display AT setting Performs PID auto tuning However when PID auto tuning has not finished after 4 hours PID auto tuning is cancelled automati...

Страница 6: ... alarm utilize common output terminals Rating 5A 0 0 to 5 0A Rating 10A 0 0 to 10 0A Rating 20A 0 0 to 20 0A Rating 50A 0 0 to 50 0A Loop break alarm action time setting 0 minutes Sets the action time to assess the Loop break alarm Setting the value to 0 disables the function Loop break alarm Alarm and Heater burnout alarm option utilize common output terminals 0 to 200 minutes Loop break alarm ac...

Страница 7: ...communication option is applied Not available if is indicated Modbus ASCII mode Modbus RTU mode Instrument number setting 0 Sets the instrument number Communication cannot be carried out unless an instrument number is individually set when communicating by connecting plural instruments in serial communication Available only when Serial communication option is added 0 to 95 Communication speed sele...

Страница 8: ...ailable for ON OFF action 5 to OUT high limit value Setting less than 0 is effective to DC current output type OUT ON OFF action hysteresis setting 1 0 Sets OUT ON OFF action Hysteresis Available only when the control action is ON OFF action Thermocouple RTD input 0 1 to 100 0 DC input 1 to 1000 The placement of the decimal point follows the selection Alarm type selection No alarm action Selects a...

Страница 9: ...or correction function This corrects the input value from the sensor When a sensor cannot be set at a location where control is desired the sensor measuring temperature may deviate from the temperature in the controlled location When controlling with plural controllers the accuracy of sensors affects the control Therefore sometimes the measured temperatures input value do not concur In such a case...

Страница 10: ...ted during Scaling low limit setting 7 Select Converter from Controller Converter function selection To activate the alarm action by Converter function set the alarm type to Process alarm If converter function is selected from Controller Converter function selection in Auxiliary function setting mode 2 the parameter below is automatically set Table 6 1 However this is applied only to the DC curren...

Страница 11: ...setting mode PV SV display Output MV indication Press the key Explanation of key This means that if is pressed the set value is saved and the controller proceeds to the next setting item Alarm setting procedure Numbers 1 to 6 are indicated on the flowchart 1 Alarm type Select an alarm type If an alarm type except for is selected items 2 to 6 are indicated and they can be set if necessary 2 Alarm a...

Страница 12: ...t action Control action Cycle action is performed according to deviation Relay contact output Non contact voltage output Changes continuously according to deviation DC current output Indicator OUT Green Lit Unlit ON OFF SV setting Proportional band ON OFF 0V DC 0 12V DC 12V DC 20mA DC 20 to 4mA DC 4 to 20mA DC Proportional band Lit 0V DC 12V DC 12 0V DC 20mA DC 4mA DC Cycle action is performed acc...

Страница 13: ...390 C W Re5 26 0 to 2315 K 320 to 2500 199 9 to 750 0 J 320 to 1800 R 0 to 3200 S 0 to 3200 B 0 to 3300 E 320 to 1500 T 199 9 to 750 0 N 320 to 2300 PL 0 to 2500 C W Re5 26 0 to 4200 Pt100 199 9 to 850 0 JPt100 199 9 to 500 0 Pt100 200 to 850 JPt100 200 to 500 Pt100 199 9 to 999 9 JPt100 199 9 to 900 0 Pt100 300 to 1500 JPt100 300 to 900 4 to 20mA DC 1999 to 9999 0 to 20mA DC 1999 to 9999 0 to 1V ...

Страница 14: ...lit Lit EVT Red High limit alarm Alarm action High Low limits alarm Low limit alarm OFF ON A1 hysteresis OFF ON SV setting A1 set point OFF ON A1 hysteresis A1 hysteresis A1 set point SV setting A1 set point A1 set point A1 set point SV setting A1 set point High Low limit range alarm Process high alarm Process low alarm OFF ON OFF ON OFF ON Alarm action A1 hysteresis A1 hysteresis A1 hysteresis A1...

Страница 15: ...s will fluctuate around the SV 1 Calculating PID constant 2 PID constant calculated 3 Controlled by the PID constant set by auto tuning C In the case of a large difference between the SV and processing temperature as the temperature is falling When AT bias is set to 20 the AT process will fluctuate at the temperature 20 higher than the SV Temperature 20 higher than the SV 1 Calculating PID constan...

Страница 16: ...seconds Off when set to 0 Derivative time 0 to 300 seconds Off when set to 0 OUT proportional cycle 1 to 120 seconds ARW 0 to 100 Manual reset Proportional band converted value Output limit 0 to 100 DC current output type 5 to 105 Not available for ON OFF action Hysteresis Thermocouple RTD input 0 1 to 100 0 DC voltage current input 1 to 1000 The placement of the decimal point follows the selectio...

Страница 17: ...ion Weight Approx 120g External dimensions 22 5 x 75 x 100mm W x H x D Material Flame resistant resin Case Color Ash gray Case Attached functions Set value lock Sensor correction Power failure countermeasure The setting data is backed up in non volatile IC memory Self diagnosis The CPU is monitored by a watchdog timer and when an abnormal status is found on the CPU the controller is switched to wa...

Страница 18: ... 9 to 550 0 206 0 to 550 0 200 to 500 207 to 550 207 to 550 199 9 to 900 0 199 9 to 999 9 211 0 to 999 9 JPt100 300 to 900 312 to 1000 312 to 1000 Indication range and Control range for thermocouple inputs except above Input range low limit value 50 100 to input range high limit value 50 100 DC current voltage input Indication range Scaling low limit value Scaling span x 1 to Scaling high limit va...

Страница 19: ... whether the sensor is burnt out Thermocouple If the input terminals of the instrument are shorted and if a value around room temperature is indicated the instrument is likely to be operating normally however the sensor may be burnt out RTD If approx 100 of resistance is connected to the input terminals between A B of the instrument and between B B is shorted and if a value around 0 32 is indicate...

Страница 20: ...larm value etc The values do not change by the keys Set value lock Lock 1 or Lock 2 is selected Release the lock selection During PID auto tuning or auto reset Cancel the auto tuning if necessary Auto reset ends 4 minutes after starting The setting indication does not change within the input range even if the keys are pressed and new values are unable to be set Scaling high limit or low limit may ...

Отзывы: