57
13. Specifications
13.1 Standard specifications
Mounting
: Flush
Setting
: Input system using membrane sheet key
Display
PV display
: 11-segment backlight LCD Red/Green/Orange, character size 12.0 x 5.4mm (H x W)
SV display
: 11-segment backlight LCD Green, character size 6.0 x 3.5mm (H x W)
MEMO display : 11-segment backlight LCD Green, character size 4.8 x 2.8mm (H x W)
Action indicators
: Backlight Orange
Accuracy (Setting and Indication)
:
Thermocouple : Within
0.2% of each input span 1digit, or within
2
(4 ),
whichever is greater
However R, S inputs, 0 to 200
(0 to 400 ): Within
6
(12 )
B input, 0 to 300
(600 ): Accuracy is not guaranteed
K, J, E, T, N inputs, less than 0
(32 ): Within
0.4% of input span 1digit
RTD
: Within
0.1% of each input span 1digit, or within
1
(2 ),
whichever is greater
DC current
: Within
0.2% of each input span 1digit
DC voltage
: Within
0.2% of each input span 1digit
Input sampling period
: 0.25 seconds
Input
Thermocouple : K, J, R, S, B, E, T, N, PL- , C (W/Re5-26)
External resistance, 100
or less
(However, B input: External resistance, 40
or less)
RTD
: Pt100, JPt100, 3-wire system
Allowable input lead wire resistance (10
or less per wire)
DC current
: 0 to 20mA DC, 4 to 20mA DC
Input impedance: 50
[50
shunt resistor (sold separately) must be
connected between input terminals.]
Allowable input current, 50mA or less [When 50
shunt resistor (sold
separately) is used]
DC voltage
: 0 to 1V DC
Input impedance (1M
or more)
Allowable input voltage (5V DC or less)
Allowable signal source resistance (2k
or less)
: 0 to 5V DC, 1 to 5V DC, 0 to 10V DC
Input impedance (100k
or more)
Allowable input voltage (15V DC or less)
Allowable signal source resistance (100
or less)
Control output (OUT1)
Relay contact : 1a, Control capacity
3A 250V AC (resistive load)
1A 250V AC (inductive load cosø=0.4)
Electrical life, 100,000 cycles
Non-contact voltage (For SSR drive): 12V DC 15%, Maximum 40mA (short circuit protected)
DC current
: 4 to 20mA DC, Load resistance, Maximum 550
Alarm 1 output
Action
: ON/OFF action
Hysteresis
: 0.1 to 100.0
( ), or 1 to 1000 (Default: 1.0 )
Output
: Relay contact 1a
Control capacity, 3A 250V AC (resistive load)
Electrical life, 100,000 cycles
Control action
PID action (with auto-tuning function)
PI action: When derivative time is set to 0
PD action (with auto-reset function): When integral time is set to 0
P action (with auto-reset function): When derivative and integral time are set to 0.
ON/OFF action: When proportional band is set to 0 or 0.0
OUT1 proportional band : 0 to 1000
(2000 ), 0.0 to 1000.0
( ) or 0.0 to 100.0%
(ON/OFF action when set to 0 or 0.0) (Default: 10 )