![Panasonic KT4 series Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/panasonic/kt4-series/kt4-series_instruction-manual_279997017.webp)
: 0 to 5V DC, 1 to 5V DC, 0 to 10V DC Input impedance (100k
or more)
Allowable input voltage (15V or less)
Allowable signal source resistance (100 or less)
Control output (OUT1)
Relay contact : 1a, Control capacity 3A 250V AC (resistive load)
1A 250V AC (inductive load cosø=0.4)
Electrical life, 100,000 cycles
Non-contact voltage (For SSR drive): 12
+2
0
V DC maximum 40mA (short circuit protected)
DC current : 4 to 20mA DC, Load resistance, maximum 550
A1 output
Action : ON/OFF action
Hysteresis
: 0.1 to 100.0
( ), or 1 to 1000
Output : Relay contact, 1a
Control capacity, 3A 250V AC (resistive load)
Electrical life, 100,000 cycles
Control action
PID action (with auto-tuning function)
PI action: When derivative time is set to 0
PD action (with auto-reset function): When integral time is set to 0
P action (with auto-reset function): When both derivative and integral times are set to 0.
ON/OFF action: When proportional band is set to 0 or 0.0
OUT1 proportional band : 0 to 1000
(2000 ), 0.0 to 999.9 ( ) or 0.0 to 100.0%
(ON/OFF action when set to 0 or 0.0)
Integral time
: 0 to 1000sec (OFF when set to 0)
Derivative time
: 0 to 300sec (OFF when set to 0)
OUT1 proportional cycle : 1 to 120sec (Not available for DC current output type)
ARW
: 0 to 100%
OUT1 output hysteresis : 0.1 to 100.0
( ), or 1 to 1000
OUT1 output limit
: 0 to 100% (DC current output type: –5 to 105%)
Circuit insulation configuration
Insulation resistance
: 10M or more, at 500V DC
Dielectric strength
: 1.5kV AC for 1 minute between input terminal and power terminal
1.5kV AC for 1 minute between output terminal and power terminal
Supply voltage
: 100 to 240V AC 50/60Hz, 24V AC/DC 50/60Hz
Allowable voltage fluctuation
: 100 to 240V AC: 85 to 264V AC, 24V AC/DC: 20 to 28V AC/DC
Power consumption
: Approx. 8VA
Ambient temperature
: 0 to 50
(32 to 122 )
Ambient humidity
: 35 to 85%RH (no condensation)
Weight
: Approx. 200
g
External dimension
: 48 x 48 x 96.5mm (W x H x D)
Material
: Flame-resistant resin (Case)
Color
: Ash gray (Case)
Attached function
:
[Set value lock], [Sensor correction], [Auto/manual control switching],
[Input abnormality indication]
Output status
OUT1
OUT2
Output status
selection when
input abnormal
Contents and
Indication
Direct action Reverse action
Direct action
Reverse action
ON (20mA) or
OUT1 high
limit value
ON or
OUT2 high limit
value
Overscale
Measured value
has exceeded
Indication range
high limit value.
"
" flashes.
OFF (4mA) or
OUT1 low
limit value
OFF (4mA) or
OUT1 low limit
value
OFF or
OUT2 low limit
value
OFF or
OUT2 low limit
value
ON (20mA) or
OUT1 high
limit value
ON or
OUT2 high limit
value
Underscale
Measured value
has dropped below
Indication range low
limit value.
"
" flashes.
OFF (4mA) or
OUT1 low
limit value
OFF (4mA) or
OUT1 low limit
value
OFF or
OUT2 low limit
value
OFF or
OUT2 low limit
value
Only for DC input and DC current output type, [Output status selection when input abnormal] is
available. For other inputs and outputs except for DC input and DC current output, the output status
will be the same one as when OFF is selected during [Output status selection when input abnormal].
For manual control, the preset MV (manipulated variable) is outputted.
Power
Insulation
Power
supply
A1
CPU
CT
input
Output
Input
EVT (A2, Heater burnout
alarm) or OUT2
15
5
4
3
9
8
1
2
12
7
6
11
10
13
14
Commu-
nication
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]