8. Action explanation 

8.1 OUT1 action   

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

8.2 EVT (Heater burnout alarm) action 

 
 
 
 
 
 

8.3 OUT1 ON/OFF action   

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 : Acts ON or OFF.

Heating (Reverse) action

Cooling (Direct) action

Control

action

Cycle action is performed according to deviation

Relay contact

output

Non-contact

voltage output

Changes continuously according to deviation

DC current

output

Indicator

(OUT1) Green

Lit

Unlit

ON

OFF

SV setting

Proportional band

ON

OFF

0V DC

0/12V DC

12V DC

+

20mA DC

20 to 4mA DC

4 to 20mA DC

Proportional band

Lit

0V DC

12V DC

12/0V DC

20mA DC

4mA DC

Cycle action is performed according to deviation

Cycle action is performed according to deviation

Cycle action is performed according to deviation

Changes continuously according to deviation

+

+

+

+

+

+

+

+

+

+

+

Unlit

4mA DC

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

SV setting

Alarm action

ON

OFF

Setting

Load current

Large

Small

Output

Indicator

Unlit

Lit

3

5

3

5

: Acts ON or OFF.

Heating (Reverse) action

Cooling (Direct) action

Control

action

Relay contact

output

Non-contact

voltage output

DC current

output

Indicator

(OUT1) Green

0V DC

12V DC

+

4mA DC

Lit

Unlit

ON

OFF

SV setting

ON

OFF

Hysteresis

Hysteresis

0V DC

12V DC

4mA DC

20mA DC

Unlit

Lit

20mA DC

+

+

+

+

+

+

+

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

7

6

SV setting

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Содержание KT4 series

Страница 1: ...function or cause fire Be sure to follow the warnings cautions and notices Not doing so could cause serious injury or accidents The contents of this instruction manual are subject to change without notice This instrument is designed to be installed in a control panel If not measures must be taken to ensure that the operator cannot touch power terminals or other high voltage sections Be sure to tur...

Страница 2: ...pressing the Mode key the set value can be registered 13 OUT OFF key The control output is turned on or off If this key is pressed for approx 1 second control output OFF function works To cancel the function press the OUT OFF key again for approx 1 second Notice When setting the specifications and functions of this controller connect terminals 1 and 2 for power source first then set them referring...

Страница 3: ...ch the mounting brackets by the holes at the top and bottom of the case and secure the controller in place with the screws Fig 3 5 1 4 Wiring Warning Turn the power supply to the instrument off before wiring or checking it Working or touching the terminal with the power switched on may result in severe injury or death due to Electric Shock 75 45 0 5 0 45 0 5 0 45 0 5 0 n x 48 3 0 5 0 Warning As th...

Страница 4: ...y contact output type use a relay according to the capacity of the load to protect the built in relay contact When wiring keep input wires thermocouple RTD etc away from AC sources or load wires to avoid external interference If A2 and Heater burnout alarm are applied together they share common output terminals Lead wire solderless terminal Use a solderless terminal with an insulation sleeve in wh...

Страница 5: ...aling high limit value 5 2 Sub setting mode Character PV display Name Function Setting range Default value SV display AT setting Auto reset setting Selects auto tuning Perform or auto reset Perform If the auto tuning is cancelled during the process P I and D values revert to the previous value When auto tuning has not finished after 4 hours it is cancelled automatically Auto reset is cancelled in ...

Страница 6: ...ing range High limit alarm Input span to input span 1 Low limit alarm Input span to input span 1 High Low limits alarm 0 to input span 1 High Low limit range alarm 0 to input span 1 Process high alarm Input range low limit value to input range high limit value 2 Process low alarm Input range low limit value to input range high limit value 2 High limit alarm with standby Input span to input span 1 ...

Страница 7: ...ilable if Serial communication option is not added or if is selected during the Communication protocol selection No parity E ven parity Odd parity Stop bit selection 1 Selects the stop bit Not available if Serial communication option is not added or if is selected during the Communication protocol selection 1 or 2 5 4 Auxiliary function setting mode 2 Character PV display Name Function Setting ran...

Страница 8: ...le if OUT2 is ON OFF action or if Heating Cooling control option is not added Air cooling oil cooling water cooling OUT2 high limit setting 100 Sets the high limit value of OUT2 Not available if OUT2 is ON OFF action or if Heating Cooling control option is not added OUT2 low limit value to 105 Setting higher than 100 is effective to DC current output type OUT2 low limit setting 0 Sets the low limi...

Страница 9: ...ed timer setting Direct Reverse control action selection Selects either Reverse Heating or Direct Cooling control action Reverse Heating action Reverse Heating Direct Cooling AT bias setting 20 Sets bias value during PID auto tuning Not available if input type is DC current or DC voltage 0 to 50 0 to 100 or 0 0 to 50 0 0 0 to 100 0 Setting item not used This item is indicated when Serial communica...

Страница 10: ...r to the instrument is supplied is indicated on the PV display while the function is working Once the control output OFF function is enabled the function cannot be released even if the power to the instrument is turned OFF and ON again To cancel the function press the key again for approx 1 second 5 7 Output manipulated variable MV indication Name function Output manipulated variable indication In...

Страница 11: ...Set value Set the value with keys Not available if is selected during A2 type selection Reverts to the PV SV display Reverts to PV SV display Press the key Main setting mode Sub setting mode 5 PV SV display Control output OFF function or Auto Manual control function Press key for approx 1sec Output MV indication Explanation of key This means that if is pressed the set value is saved and the contro...

Страница 12: ...o deviation Cycle action is performed according to deviation Cycle action is performed according to deviation Changes continuously according to deviation Unlit 4mA DC 7 6 7 6 7 6 7 6 7 6 7 6 7 6 7 6 7 6 7 6 7 6 7 6 7 6 7 6 7 6 7 6 7 6 7 6 SV setting Alarm action ON OFF Setting Load current Large Small Output Indicator Unlit Lit 3 5 3 5 Acts ON or OFF Heating Reverse action Cooling Direct action Co...

Страница 13: ... with the keys Default value A2 action delayed timer PV SV Set value Set the value with the keys Not available if is selected during A2 type selection A2 hysteresis PV SV Set value Set the value with the keys Not available if is selected during A2 type selection AT bias PV SV Set value Set the value with the keys Available for thermocouple RTD input 2 Setting item not used PV SV Set value Do not s...

Страница 14: ...h standby Low limit alarm with standby OFF ON OFF ON OFF ON Alarm action A1 hysteresis A1 hysteresis A1 hysteresis A1 set point A1 set point SV setting SV setting A1 set point A1 set point A1 set point SV setting A1 set point Standby functions in this section Cycle action is performed according to deviation OFF ON SV setting OFF ON 7 7 7 6 6 6 6 7 12V DC 6 7 12 0V DC 6 7 0V DC 6 7 20mA DC 6 7 20 t...

Страница 15: ...ously according to deviation Non contact voltage output OUT1 DC current output OUT1 Non contact relay output OUT2 Indicator OUT1 Green Indicator OUT2 Yellow Lit Unlit Lit Unlit Cycle action is performed according to deviation 3 3 3 5 5 5 7 7 7 6 6 6 6 7 12V DC 6 7 12 0V DC 6 7 0V DC 6 7 20mA DC 6 7 20 to 4mA DC 6 7 4mA DC OFF ON OFF ON SV setting Heating action Cooling action Heating p band Coolin...

Страница 16: ...ver is greater DC current Within 0 2 of each input span 1digit DC voltage Within 0 2 of each input span 1digit Input sampling period 0 25 seconds Input Thermocouple K J R S B E T N PL C W Re5 26 External resistance 100 or less However for B input External resistance 40 or less RTD Pt100 JPt100 3 wire system Allowable input lead wire resistance 10 or less per wire DC current 0 to 20mA DC 4 to 20mA ...

Страница 17: ...ltage 100 to 240V AC 50 60Hz 24V AC DC 50 60Hz Allowable voltage fluctuation 100 to 240V AC 85 to 264V AC 24V AC DC 20 to 28V AC DC Power consumption Approx 8VA Ambient temperature 0 to 50 32 to 122 Ambient humidity 35 to 85 RH no condensation Weight Approx 200g External dimension 48 x 48 x 96 5mm W x H x D Material Flame resistant resin Case Color Ash gray Case Attached function Set value lock Se...

Страница 18: ... located at 0 32 Power failure countermeasure The setting data is backed up in the non volatile memory Warm up indication After the p ower supply to the instrument is turned on the sensor input character an d temperature unit are indicated on the PV display and input range high limit value is indicated on the SV display for 3 seconds For DC current and voltage inputs the scaling high limit value i...

Страница 19: ... working Press the key for approx 1 second to release the function is flashing on the PV display Thermocouple RTD or DC voltage 0 to 1V DC is burnt out Change each sensor How to check whether the sensor is burnt out Thermocouple If the input terminal of the instrument is shorted and if a value around room temperature is indicated the instrument is likely to be operating normally however sensor may...

Страница 20: ...n ungrounded type sensor There may be equipment that interferes with or makes noise near the controller Keep equipment that interferes with or makes noise away from the controller The PV display is indicating Internal memory is defective Contact our agency or us 11 2 Key operation Problem Presumed cause and solution Unable to set the SV P I D proportional cycle or alarm setting The values do not c...

Отзывы: