12-16
WR904
Relay No.
Name
Description
R9040
TOOL port operation
mode flag
-
Turns on when the general-purpose communication
function is being used
-
Goes off when the computer link function is being used.
R9041
COM1 port PLC link flag
Turn on while the PLC link function is used.
R9042
COM2 port
communication mode
flag
-
Goes on when the general-purpose serial communication
is used.
-
Goes off when the MEWTOCOL is used.
R9043
Not used
-
R9044
COM1 port SEND/RECV
instruction execution
flag
Monitors whether the F145 (SEND) or F146 (RECV)
instructions can be executed or not.
Off: None of the above mentioned instructions can be
executed. (During executing the instruction)
On: One of the above mentioned instructions can be
executed.
R9045
COM1 port SEND/RECV
instruction execution
end flag
Monitors if an abnormality has been detected during the
execution of the F145 (SEND) or F146 (RECV)
instructions as follows:
Off: No abonormality detected.
On: An abnormality detected. (communication error)
The error code is stored in DT90039.
End code: DT90124
R9046
Not used
-
R9047
COM2 port
communication error
flag
-
Goes on if a transmission error occurs during data
communication.
-
Goes off when a request is made to send data, using the
F159 (MTRN) instruction.
R9048
COM2 port port
reception done flag
during general-purpose
communicating
-
Turn on when the terminator is received during general-
purpose serial communication.
R9049
COM2 port transmission
done flag during
general-purpose
communication
-
Goes on when transmission has been completed in
general-purpose serial communication.
-
Goes off when transmission is requested in general-
purpose communication.
R904A
COM2 port SEND/RECV
instruction execution
flag
Monitors whether the F145 (SEND) or F146 (RECV)
instructions can be executed or not.
Off: None of the above mentioned instructions can be
executed. (During executing the instruction)
On: One of the above mentioned instructions can be
executed.
R904B
COM2 port SEND/RECV
instruction execution
end flag
Monitors if an abnormality has been detected during the
execution of the F145 (SEND) or F146 (RECV)
instructions as follows:
Off: No abonormality detected.
On: An abnormality detected. (communication error)
The error code is stored in DT90039.
End code: DT90125
R904C to
R904D
Not used
-
R904E
Circular interpolation
control flag
Goes on when the F176 (SPCH) circular interpolation
instruction is executed.
R904F
Circular interpolation
data overwrite
confirmation flag
It is used to overwrite next data when the circular
interpolation instruction is used in the continuation mode.
Note) R9040 to R904F can be changed during 1 scan.
WR905
Relay No.
Name
Description
R9050
MEWNET-W0
PLC link transmission
error flag
When using MEWNET-W0
-
Turns on when a transmission error occurs at PLC link.
-
Turns on when there is an error in the PLC link area
settings.
R9051 to
R905F
Not used
Содержание FP E Series
Страница 1: ......
Страница 16: ......
Страница 17: ...Chapter 1 Functions and Restrictions of the Unit ...
Страница 28: ...1 12 ...
Страница 29: ...Chapter 2 Specifications and Functions of the Unit ...
Страница 37: ...2 9 Circuit diagram C32 Y0 Y1 Y3 Y4 C28 Y0 Y1 Y3 Y4 Y2 Y5 to YF Y2 Y5 to YB ...
Страница 48: ...2 20 ...
Страница 49: ...Chapter 3 Expansion ...
Страница 56: ...3 8 Terminal layout diagram Note The numbers in the connector are for the first expansion ...
Страница 61: ...Chapter 4 I O Allocation ...
Страница 66: ...4 6 ...
Страница 67: ...Chapter 5 Installation and Wiring ...
Страница 90: ...5 24 ...
Страница 91: ...Chapter 6 High speed counter Pulse Output and PWM Output functions ...
Страница 116: ...6 26 ...
Страница 121: ...6 31 ...
Страница 125: ...6 35 Pulse output diagram ...
Страница 131: ...6 41 ...
Страница 139: ...6 49 ...
Страница 141: ...6 51 ...
Страница 144: ...6 54 Program Continued on the next page ...
Страница 145: ...6 55 ...
Страница 147: ...6 57 Program ...
Страница 151: ...Chapter 7 Communication Cassette ...
Страница 202: ...7 52 Procedure of communication In the following example the Micro Imagechecker is connected to COM1 port ...
Страница 210: ...7 60 The values of DT50 and DT51 are written in DT0 and 1 of PLC ...
Страница 238: ...7 88 ...
Страница 239: ...Chapter 8 Self Diagnostic and Troubleshooting ...
Страница 247: ......
Страница 248: ......
Страница 249: ...Chapter 9 Precautions During Programming ...
Страница 260: ...9 12 Example 2 Using the CT instruction between JP and LBL instructions ...
Страница 268: ...9 20 ...
Страница 269: ...Chapter10 Specifications ...
Страница 286: ......
Страница 287: ...Chapter 11 Dimensions ...
Страница 290: ...11 4 11 1 3 Expansion Unit FPG XY64D2T FPG XY64D2P FPG EM1 ...
Страница 293: ...Chapter 12 Appendix ...
Страница 297: ...12 5 ...
Страница 437: ...12 145 12 7 ASCII Codes ...
Страница 439: ......
Страница 440: ......