Operation Manual
FT128 Rev 2.4
89
21.2
Disable Zone / Address (H2/B2)
Up to 100
addressable alarm points (also addressable manual call points), connected to
the COM loop, can be individually disabled.
Disabled alarm points (zone – address) are listed in menu H4/U1.
Disabled alarm points (zone – address) can be automatically re-enabled or via menu
H2/B6.
Note: The sensor values for disabled analogue smoke detectors in NORMAL mode will
not be used for calculation of the week average sensor value, i.e. only the values saved
before and after the disablement will be used for this calculation.
Action
Text in display
Comments
"Access"
Log on to FT128 as shown in
page 35.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B2.
Disable zone / address
ACCEPT? B2
"A"
Disable zone: 0 0 Address: 00
ACCEPT?
Write zone number
and address
e.g. 01 - 01
Disable zone: 01 Address: 01
ACCEPT?
Press "A" to accept.
"A"
Automatic re-enabling: 0 (0=No,1=Yes)
Time: HH:MM ACCEPT?
Press "1" for auto re-
enabling and accept or
change the time (max. 24
hours).
Press "A" to accept. LED
"Disablements" (L8) will
light up.
(Default is current time + 3 hours)
"A"
Zone 01 address 01 is disabled
"A"
Disable zone: 0 0 Address: 00
ACCEPT?
If more disablements
required, continue as
above otherwise, press
"Return" to menu B2.
"Return"
Disable zone-address
ACCEPT? B2
Scroll or press "Return" to
menu H2.
"Return"
Disable or re-enable
ACCEPT? H2
Scroll or press "Return"
Содержание Firetracker FT128
Страница 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Страница 2: ...2 This page has deliberately been left blank ...
Страница 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Страница 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Страница 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Страница 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...