Action
Text in display
Comments
"2"
"A"
End test mode zone: 01
ACCEPT? L
This is a list in which you can
scroll between all the zones
in test mode. Select or type
the zone number and press
"A". When no more zones
are in test mode
--- List is empty ---
will be shown and the LED
"Test mode" (L9) is turned
OFF. Press "Return" to D2.
--- List is empty ---
"Return"
End zone in test mode
ACCEPT? D2
Press return to H7
"Return"
Perform zone test
ACCEPT? H7
Notes:
If an alarm point (e.g. a manual call point) is in alarm state when the test mode is ended,
there will be a fire alarm activated.
When the "Fire door closing" function is used, the fire door(s) will be closed when the
zone involved is set in test mode.