Operation Manual
FT128 Rev 2.4
133
27.10
Reset activated output (H8/S10)
Output(s) activated via menu H8/S9 have to be reset via this menu (H8/S10).
Note: Only output types that are activated will be shown and possible to select.
Action
Text in display
Comments
"
Access
"
Log on to FT128 as
shown in page 35.
Scroll to menu H8.
Maintenance
ACCEPT? H8
"A"
Acknowledge SERVICE signal
ACCEPT? S1
Scroll to menu S10
Reset activated output
ACCEPT? S10
"A"
Reset output type: 0
0=Loopunit 1=S 2=R0 3=EXPB ACCEPT?
Only output types that
are activated will be
shown. Loop unit=3361
or 3364
S=S0-S1
R0=R0
EXPB= 4581 or 4583
Depending on if 0, 1,
2 or 3 is selected
one of the
alternatives will be
shown.
Reset output: 0, technical address 000
ACCEPT? L
L=A list in which you
can scroll. Select the
output to reset and
press "A".
Reset S0
ACCEPT? L
Reset R0
ACCEPT? L
Reset output: 0, expansion board 0
ACCEPT? L
"A"
Reset output type: 0
0=Loop unit 1=S 2=R0 3=EXPB ACCEPT?
Only output types that
are activated will be
shown.
When all outputs are
reset,
--- List is empty ---
will
be shown.
"Return"
Reset activated output
ACCEPT? S10
Scroll or press "Return"
to menu H8.
"Return"
Maintenance
ACCEPT? H8
Scroll or press "Return".
Содержание Firetracker FT128
Страница 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Страница 2: ...2 This page has deliberately been left blank ...
Страница 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Страница 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Страница 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Страница 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...