Operation Manual
FT128 Rev 2.4
104
Low sensitivity (3.6%) & Slow detection (35 s)
L-35
Heat algorithm, Class A1
A1
Heat algorithm, Class A2 (S)
A2
Heat algorithm, Class B (S)
B
Decision algorithm
Dec
Default is
N-15
and
A1
respectively.
Algorithm
Detector 4400 in Advanced mode.
Abbreviation
Normal area
Normal
Clean area
Clean
Cooking-Welding area
Welding
Heater area
Heater
Smoke-Steam area
Smoke
Default is Normal.
Algorithm
Detector 4401 in Advanced mode.
Abbreviation
Normal area
Normal
Clean area
Clean
Smoke-Steam area
Smoke
Default is Normal.
62
Analogue multi detector 4300 only.