Operation Manual
FT128 Rev 2.4
17
3.4.1
LED Indicators and Push Button
LED’s and push buttons are contained on the front panel display and are described in the
tables below. See also Figure 3 above, for the LEDs and push buttons.
3.4.1.1
Fire Brigade Panel Display and Control
Table 4 Fire Brigade Panel LED Indicators and Push Buttons
No.
Label
Colour
Indicating / Action
L1
Fire
5 x Red
Fire alarm, Quiet alarm, etc. See Alarm
L2
Alarms queued
2 x Red
More than one unit / zone has generated fire
alarm.
Use push button "Alarms queued" (P1) to
scroll amongst the alarm points (zone-address).
L3
Extinguishing
Red
Output(s) for extinguishing equipment
(or a programmable input type "Extinguishing" is
activated).
L4
Ventilation
Yellow
Output(s) for fire/smoke ventilation equipment
activated (or a programmable input type
"Ventilation" is activated.)
L5
Fire Brigade TX
Red
Output for “Fire alarm” for Fire Brigade TX (routing
equipment)
activated. Or a programmable input(s)
type "Activated routing equipment" is activated. Or
test of routing equipment in progress (see menu
H1).
L6
Operation
Green
Power on, i.e. the FT128 power supply (switch
mode power supply and/or batteries) are
connected and working properly.
P1
Alarms queued
BLACK
Used, when LEDs "Alarms queued" (L2) are lit, to
scroll/browse through the queued alarms (zones).
P2
Silence buzzer
Yellow
Used to silence the buzzer in FT128
P3
Silence Alarm
devices
Red
Used to silence devices configured as “Alarm
devices” such as sounders or OWS (i.e. to "reset"
outputs for alarm devices).
P4
Reset
Green
Used to reset the fire alarm(s), has to be pressed
for > 0.5 Secs
P5
Disable
Yellow
Used to disable active alarm(s), all outputs of the
device or zone in alarm will be disabled.
9
In the New Zealand convention also "Acknowledged alarm" (ACK).
10
L3, L4 and L5 can as an alternative be programmed to indicate when a programmable input is activated, i.e. input trigger
condition "Extinguishing system released", "Activated fire ventilation" and "Activated routing equipment" respectively (e.g. L5
can be turned on when a programmable input is activated by an activated routing equipment output). L5 is turned on until all
fire alarms are reset.
11
Via EBLWin can be set if the alarm devices are to be continuously off / disabled or re-sound for a new alarm.
Содержание Firetracker FT128
Страница 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Страница 2: ...2 This page has deliberately been left blank ...
Страница 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Страница 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Страница 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Страница 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...