Troubleshooting
9 Troubleshooting
This section contains information and procedures for solving possible
problems with
EVERVOLT Hybrid Inverter
, and provides you with
troubleshooting tips to identify and solve most problems that could occur
with
EVERVOLT Hybrid Inverter
.
Troubleshooting
69
68
This section will help you narrow down the source of the problems you may
encounter. Please read the following troubleshooting steps.
Check warnings or fault messages on the myEVERVOLT Cloud. If a message is
displayed, record it before doing anything further operation.
AFD Self Check
Fault
Arc Detect Fault
PV Conn Dir Fault
PV Reverse Connection Fault
Ÿ
Re-connect the PV correctly
BAT Volt Fault
Battery Voltage Over high or Over low Fault
Ÿ
Check if the battery input voltage is within the normal range
Ÿ
Please contact Panasonic Technical Support
EPO Fault
EPO Activated or Inverter Emergency Off
BI Comm Fault
Communication Fault between Inverter and Smart Box
Ÿ
Check if the RS485 communication cable of Smart Box connects to
communication board of inverter.
Ÿ
Please contact Panasonic Technical Support
DC Arc occurs or DC Arc Check Fault
Ÿ
Please check if there is any visible arc vestige firstly
Ÿ
Clear the PV input and solar battery board connects normally
Ÿ
If Arc is detected five times in one hour, please manually clear Arc.
Otherwise, it will re-connect to grid in five minutes
Faults
Diagnosis and solution
Update File Fail
File Upgrade Fault
Ÿ
Check if the file and the folder are correct
Ÿ
Please contact Panasonic Technical Support
Udisk Update
Fault
U Disk Upgrade Fault
Ÿ
Check if the U disk is correctly plugged and the file is correct
Ÿ
Please contact PanasonicTechnical Support
Meter Fault
Meter Communication Fault
Ÿ
Check if the communication cable between inverter and Smart
Box connects normally or contact Panasonic Technical Support
BMS_Lost
Update Fault
Software Upgrade Fault
Ÿ
Check if the communication cable between inverter and Smart Box and
re-upgrade the software
Ÿ
Check the communication cable between control board and
communication board and re-upgrade the software
Ÿ
Check the communication cable between inverter and battery
Ÿ
Or contact Panasonic Technical Support
PV Volt Fault
PV Voltage Out of Normal Range
Ÿ
Decrease the PV voltage
Ÿ
Or contact Panasonic Technical Support
DCI OCP Fault
DCI over current protection Fault
Ÿ
Please contact Panasonic Technical Support
DCV OVP Fault
DCV EPS over voltage protection Fault
Ÿ
Please contact Panasonic Technical Support
BMS Communication Lost
Ÿ
Check the communication connection between the battery and the
inverter
Ÿ
Please contact Panasonic Technical Support
Faults
Diagnosis and solution
Bat Current
Imbalance
The Firmware Fault of Battery Charge
• Please contact Panasonic Technical Support
Bat ConDir Fault
The Positive and Negative Pole of Battery Connected Reversely
Ÿ
Re-connect the battery.
AFDI Model Self Check Fault
Ÿ
Please check if the AFDI module connects normally
Ÿ
Or contact Panasonic Technical Support